1
vacon • 7
Safety
1.6
Earthing and earth fault protection
The VACON
®
20 CP AC drive must always be earthed with an earthing conductor connected to
the earthing terminal marked with
.
Since the touch current exceeds 3.5 mA AC (for the three-phase version), according to
EN61800-5-1, the drive shall have a fixed connection and provision of an additional terminal for
a second protective earthing conductor of the same cross-sectional area as the original pro-
tective earthing conductor.
Three screws (for the three-phase version) are provided for: the ORIGINAL protective earthing
conductor, the SECOND protective conductor and the MOTOR protective conductor (the cus-
tomer can choose the screw for each one). See Figure 1 for the location of the three screws in
the two possible options available.
Figure 1. Protective earthing connections MS2 and MS3, three-phase version.
In VACON
®
20 CP, the phase conductor and the corresponding protective earthing conductor
can be of the same cross-sectional area, provided they are made of the same metal (because
the cross-sectional area of the phase conductor is less than 16 mm
2
).
CAUTION!
Содержание 20 CP
Страница 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Страница 2: ......
Страница 6: ...vacon 3 ...
Страница 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Страница 18: ...1 vacon 15 Safety ...
Страница 24: ...vacon 21 Receipt of delivery 2 ...
Страница 36: ...3 vacon 33 Mounting ...
Страница 48: ...4 vacon 45 Power cabling ...
Страница 64: ...5 vacon 61 Control unit ...
Страница 111: ...Safe Torque Off vacon 108 Service support find your nearest Vacon service center at www vacon com 9 ...