1
vacon • 11
Safety
1.9
Cooling System
VACON
®
20 CP is available as a cold-plate solution. Customers have to enclose it in their own
housing and provide a suitable heatsink. However under maximum operating conditions the
unit should not exceed the following temperatures:
•
Temperature around the polymeric enclosure (of VACON
®
20 CP): max. 70 °C (158 °F)
•
Temperature at the cooling-plate (of VACON
®
20 CP): max. 85 °C (185 °F)
Please, contact your local Vacon distributor if you need further details or support to dimension
the cooling system in your final application.
NOTE:
Up to 1.5 kW (Voltage range 380-480V) and 0.75 kW (Voltage range 208-240V) the drive
is not equipped with external cooling fan.