Safety
vacon • 10
Service support: find your nearest Vacon service center at www.vacon.com
1
Figure 4. Insulation system (single-phase version).
1.8
Compatibility with RCDs
(*)
Only for MS3.
(**)
The relays may be used also with DVC A circuits. This is possible only if both
relays are used for DVC A circuitry:
to mix Mains and DVC A is not allowed.
This product can cause a d.c. current in the protective earthing conductor. Where
a
residual current-operated protective (RCD) or monitoring (RCM) device
is
used for protection in case of direct or indirect contact, only an RCD or RCM of
Type B
is allowed on the supply side of this product.
POWER UNIT
L
N
U
V
W
R01 __
R02 __
10Vref __
Analog Inputs __
Digital Inputs__
Analog Output __
24V __
RS485 __
Keypad
CONTROL UNIT
Reinforced
Mains
DVC A
DVC A or Mains
(**)
DC-
DC+
Содержание 20 CP
Страница 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Страница 2: ......
Страница 6: ...vacon 3 ...
Страница 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Страница 18: ...1 vacon 15 Safety ...
Страница 24: ...vacon 21 Receipt of delivery 2 ...
Страница 36: ...3 vacon 33 Mounting ...
Страница 48: ...4 vacon 45 Power cabling ...
Страница 64: ...5 vacon 61 Control unit ...
Страница 111: ...Safe Torque Off vacon 108 Service support find your nearest Vacon service center at www vacon com 9 ...