Commissioning
vacon • 64
Service support: find your nearest Vacon service center at www.vacon.com
6
6.2
Changing EMC protection class
If your supply network is an IT (impedance-grounded) system but your AC drive is EMC-pro-
tected according to class C1 or C2 you need to modify the EMC protection of the AC drive to
EMC-level T (C4). This is done as described below:
6.2.1
Changing EMC protection class - MS2 three-phase version
Figure 35.Changing of the EMC class in MS2 (three-phase version).
Warning! Do not perform any modifications on the AC drive when it is connected
to mains.
1
Remove the three screws on the EMC plate from the unit.