Technical data
vacon • 72
Service support: find your nearest Vacon service center at www.vacon.com
7
7.2
Brake resistors
Make sure that the resistance is higher than the minimum resistance defined. The power han-
dling capacity must be sufficient for the application. Brake chopper is available only in three-
phase version.
Recommended brake resistor values for Vacon 20 CP AC drives:
Mains Voltage 3AC 208-240 V, 50/60 Hz
Frame
Type
Minimum Resistance
recommended [Ohm]
MS2
0004
50
0005
50
0007
50
MS3
0011
25
0012
25
0017
25
Table 33. Brake resistor ratings, 3AC 208-240V.
Mains Voltage 3AC 380-480 V, 50/60 Hz
Frame
Type
Minimum Resistance
recommended [Ohm]
MS2
0003
100
0004
100
0005
100
0006
100
0008
100
MS3
0009
50
0012
50
0016
50
Table 34. Brake resistor ratings, 3AC 380-480V.