61
Table 64 — Economizer Configuration Table
ECONOMIZER OPERATION CONFIGURATION — The
configuration items in the
E.CFG
menu group affect how
the economizer modulates when attempting to follow an
economizer cooling setpoint. Typically, they will not need
adjustment. In fact, it is strongly advised not to adjust these
configuration items from their default settings without first
consulting a service engineering representative.
In addition, the economizer cooling algorithm is designed to
automatically slow down the economizer actuator’s rate of
travel as outside air temperature decreases.
ECONOMIZER DIAGNOSTIC HELP — Because there are
so many conditions which might disable the economizer from
being able to provide free cooling, the control has a display
table to identify these potentially disabling sources. The user
can check
ACTV
, the “Economizer Active” flag. If this flag is
set to Yes there is no reason to check
DISA
(Economizer
Disabling Conditions). If the flag is set to No, this means that at
least one or more of the flags under the group
DISA
are set
to Yes and the user can discover what is preventing the econo-
mizer from performing free cooling by checking the table.
The economizer’s reported and commanded positions
are also viewable, as well as outside air temperature, relative
humidity, enthalpy and dew point temperature.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
EC.EN
Economizer Installed?
Yes/No
ECON_ENA
Yes
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
EC.MX
Economizer Max.Position
0 - 100
%
ECONOMAX
98
EP.MS
Economizer Position at Minimum VFD Speed
0 - 100
%
EPOSMNFS
5
EP.XS
Economizer Position at Maximum VFD Speed
0 - 100
%
EPOSMXFS
5
E.TRM
Economzr Trim For SumZ ?
Yes/No
ECONTRIM
Yes
E.SEL
Econ ChangeOver Select
0 - 3
ECON_SEL
0
DDB.C
Diff Dry Bulb RAT Offset
0 - 3
dF
EC_DDBCO
0
OA.E.C
OA Enthalpy ChgOvr Selct
1 - 5
OAEC_SEL
4
OA.EN
Outdr.Enth Compare Value
18 - 32
OAEN_CFG
24
OAT.L
High OAT Lockout Temp
-40 - 120
dF
OAT_LOCK
60
O.DEW
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
ORH.S
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
E.TYP
Economizer Control Type
1 - 3
ECON_CTL
1
EC.SW
Economizer Switch Config
0 - 2
ECOSWCFG
0
E.CFG
ECON.OPERATION CONFIGS
E.P.GN
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
E.RNG
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
E.SPD
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
E.DBD
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
UEFC
UNOCC.ECON.FREE COOLING
FC.CF
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
FC.TM
Unoc Econ Free Cool Time
0 - 720
min
UEFCTIME
120
FC.L.O
Un.Ec.Free Cool OAT Lock
40 - 70
dF
UEFCNTLO
50
T.24.C
TITLE 24 FDD
LOG.F
Log Title 24 Faults
Yes/No
T24LOGFL
No
EC.MD
T24 Econ Move Detect
1 to 10
dF
T24ECMDB
1
EC.ST
T24 Econ Move SAT Test
10 to 20
%
T24ECSTS
10
S.CHG
T24 Econ Move SAT Change
0 to 5
dF
T24SATMD
0.2
E.SOD
T24 Econ RAT-OAT Diff
5 to 20
dF
T24RATDF
15
E.CHD
T24 Heat/Cool End Delay
0 to 60
min
T24CHDLY
25
ET.MN
T24 Test Minimum Pos.
0 to 50
%
T24TSTMN
15
ET.MX
T24 Test Maximum Pos.
50 to 100
%
T24TSTMX
85
SAT.T
SAT Settling Time
10 to 900
sec
SAT_SET
240
Fig. 12 — Custom Changeover Curve Example
A48-7731
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...