68
Table 69 — Indoor Air Quality Configuration
IAQ Discrete Input Config (
Configuration
IAQ
AQ.CF
IQ.I.C
) — This configuration is used to set the type of IAQ
sensor. The following are the options:
•
IQ.I.C
= 0 (No Discrete Input) — This is used to indicate
that no discrete input will be used and the standard IAQ
sensor input will be used.
•
IQ.I.C
= 1 (IAQ Discrete Input) — This will indicate
that the IAQ level (high or low) will be indicated by
the discrete input. When the IAQ level is low, the
economizer minimum position will be
Configuration
IAQ
DCV.C
IAQ.M
.
•
IQ.I.C
= 2 (IAQ Discrete Input with Minimum Position
Override) — This will indicate that the IAQ level (high
or low) will be indicated by the discrete input and the
economizer minimum position will be the IAQ override
position,
IQ.O.P
(when high).
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
IAQ.M
IAQ Demand Vent Min.Pos.
0 - 100
%
IAQMINP
0
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
0 - 4
IAQANCFG
0
IQ.A.F
IAQ 4-20 ma Fan Config
0 - 2
IAQANFAN
0
IQ.I.C
IAQ Discrete Input Config
0 - 2
IAQINCFG
0
IQ.I.F
IAQ Disc.In. Fan Config
0 - 2
IAQINFAN
0
OQ.A.C
OAQ 4-20ma Sensor Config
0 - 2
OAQANCFG
0
AQ.SP
AIR QUALITY SETPOINTS
IQ.O.P
IAQ Econo Override Pos.
0 - 100
%
IAQOVPOS
100
DAQ.L
Diff.Air Quality LoLimit
0 - 1000
DAQ_LOW
100
DAQ.H
Diff. Air Quality HiLimit
100 - 2000
DAQ_HIGH
700
D.F.OF
DAQ PPM Fan Off Setpoint
0 - 2000
DAQFNOFF
200
D.F.ON
DAQ PPM Fan On Setpoint
0 - 2000
DAQFNON
400
IAQ.R
Diff. AQ Responsiveness
-5 - 5
IAQREACT
0
OAQ.L
OAQ Lockout Value
0 - 2000
OAQLOCK
0
OAQ.U
User Determined OAQ
0 - 5000
OAQ_USER
400
AQ.S.R
AIR QUALITY SENSOR RANGE
IQ.R.L
IAQ Low Reference
0 - 5000
IAQREFL
0
IQ.R.H
IAQ High Reference
0 - 5000
IAQREFH
2000
OQ.R.L
OAQ Low Reference
0 - 5000
OAQREFL
0
OQ.R.H
OAQ High Reference
0 - 5000
OAQREFH
2000
IAQ.P
IAQ PRE-OCCUPIED PURGE
IQ.PG
IAQ Purge
Yes/No
IAQPURGE
No
IQ.P.T
IAQ Purge Duration
5 - 60
min
IAQPTIME
15
IQ.P.L
IAQ Purge LoTemp Min Pos
0 - 100
%
IAQPLTMP
10
IQ.P.H
IAQ Purge HiTemp Min Pos
0 - 100
%
IAQPHTMP
35
IQ.L.O
IAQ Purge OAT Lockout
35 - 70
dF
IAQPNTLO
50
25
20
15
10
5
0
0
10
20
30
40
50
60
70
80
70
80
FIXED MIN WITH OFFSET
FIXED MINIMUM
DUA
L SETPOINT
WITH OFFSET
DUAL
SETPOINT
ECONOPOS %
SFAN_VFD %
90
Fig. 16 — Example of Dual Setpoint Versus Fixed Minimum Economizer Position
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...