31
Condenser Type (
CND.T
) — This configuration specifies the
type of condenser installed in the unit. Configuration
CND.T
is
set to 0 if the condenser is a round tube, plate fin coil (RTPF).
Configuration
CND.T
is set to 1 if the condenser is a micro-
channel heat exchanger coil (MCHX).
MAT Calc Config (
MAT.S
) — This configuration gives the
user three options in the processing of the mixed-air tempera-
ture (MAT) calculation:
•
MAT.S
= 0
There will be no MAT calculation.
•
MAT.S
= 1
The control will attempt to learn MAT over time. Any time
the system is in a vent mode and the economizer stays at a
particular position for long enough, MAT is set to equal
EDT. Using this, the control has an internal table whereby it
can more closely determine the true MAT value.
•
MAT.S
= 2
The control will not attempt to learn MAT over time.
To calculate MAT linearly, the user should reset the MAT
table entries by setting
MAT.R
to YES. Then set
MAT.S
= 2
.
The control will calculate MAT based on the position of the
economizer, outside-air temperature, and return-air
temperature.
To freeze the MAT table entries, let the unit run with
MAT.S
= 1
. Once sufficient data has been collected, change
MAT.S
= 2
. Do not reset the MAT table.
Reset MAT Table Entries? (
MAT.R
) — This configuration al-
lows the user to reset the internally stored MAT learned config-
uration data back to the default values. The defaults are set to a
linear relationship between the economizer damper position
and OAT and RAT in the calculation of MAT.
MAT Outside Air Position Default (
MAT.D
) — This config-
uration is used to calculate MAT when the economizer option
is disabled. The configuration is adjustable from 0 to 100%
outside air. This defines the fixed ventilation position that will
be used to correctly calculate MAT.
Altitude……..In Feet: (
ALTI
) — The control does not in-
clude a barometric pressure sensor to determine altitude. The
altitude must be defined the calculation of enthalpy and cfm.
The altitude parameter is used to set up a default barometric
pressure for use with calculations. The effect of barometric
pressure in these calculations is not great, but could have an
effect depending on the installed elevation of the unit. If the
unit is installed at a particularly high altitude and enthalpy or
cfm are being calculated, set this configuration to the current
elevation.
Start Up Delay Time (
DLAY
) — This option delays the unit
from operating after a power reset. The configuration may be
adjusted from 0 to 900 seconds of delay.
TSTAT — Both Heat and Cool (
STAT
) — This option, if en-
abled, allows both heating and cooling requests to be made at
the same time. If the unit is configured for staged gas heat, and
if a cooling request is initiated (Y1 or Y2), then W1 initiates re-
heat and W2 initiates dehumidification.
Auxiliary Relay Configuration (
AUX.R
) — This option con-
figures the auxiliary relay on the MBB (RLY11). The function
of this relay is configurable in the following ways:
•
AUX.R
= 0
(Alarm Output) — The relay is used for remote
annunciation of an alarm state.
•
AUX.R
= 1
(Dehum-Reheat) — The relay is used as a dehu-
midification/reheat output.
•
AUX.R
= 2
(Occup. State) — The relay is used to reflect
occupancy. When the control is in occupied mode, the relay
will be ON. When the control is in unoccupied mode, the
relay will be OFF.
•
AUX.R
= 3
(S. Fan State) — The relay is used to reflect the
supply fan commanded state. When the supply fan is on, the
relay will be ON. When the supply fan is off, the relay will
be OFF.
Space Temp Sensor (
SPT.S
) — If a space temperature sensor
is installed, this configuration should be enabled.
Space Temp Offset Sensor (
SP.O.S
) — If a space tempera-
ture sensor with a space temperature offset slider is installed
(T56), this configuration should be enabled.
Space Temp Offset Range (
SP.O.R
) — If a space temperature
offset sensor is installed, it is possible to configure the range of
the slider by adjusting this range configuration.
Return RH Sensor (
RRH.S
) — If a return air relative humidi-
ty sensor is installed, this configuration should be enabled.
Filter Status Switch Enabled? (
FLT.S
) — If a filter status
switch is installed, enable this configuration to begin the moni-
toring of the filter status input (
Inputs
GEN.I
FLT.S
). See
the Dirty Filter Switch section on page 57 for more details on
installation and operation.
Table 32 — Unit Configuration
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULTS
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 - 6
CTRLTYPE
4
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 - 1
FAN_MODE
1
RM.CF
Remote Switch Config
0 - 3
RMTINCFG
0
CEM
CEM Module Installed
Yes/No
CEM_BRD
No
TCS.C
Temp.Cmp.Strt.Cool Factr
0 - 60
min
TCSTCOOL
0
TCS.H
Temp.Cmp.Strt.Heat Factr
0 - 60
min
TCSTHEAT
0
SFS.S
Fan Fail Shuts Down Unit
Yes/No
SFS_SHUT
No
SFS.M
Fan Stat Monitoring Type
0 - 2
SFS_MON
0
VAV.S
VAV Unocc.Fan Retry Time
0 - 720
min
SAMPMINS
50
SIZE
Unit Size (20-60)
20 - 60
UNITSIZE
20
DP.XR
Discharge Press. Transducers
Yes/No
DP_TRANS
No
SP.XR
Suct. Pres. Trans. Type
0 - 1
SPXRTYPE
0
RFG.T
REFRIG: 0=R22, 1=R410A
0 - 1
REFRIG_T
Unit dependent
CND.T
CND HX TYP: 0=RTPF, 1=MCHX
0 - 1
COILTYPE
Unit dependent
MAT.S
MAT Calc Config
0 - 2
MAT_SEL
1
MAT.R
Reset MAT Table Entries?
Yes/No
MATRESET
No
MAT.D
MAT Outside Air Default
0-100
%
MATOADOS
20
ALTI
Altitude……..in feet:
0 - 60000
ALTITUDE
0
DLAY
Startup Delay Time
0 - 900
sec
DELAY
0
STAT
TSTAT-Both Heat and Cool
Yes/No
TSTATALL
No
AUX.R
Auxiliary Relay Config
0 - 3
AUXRELAY
0
SENS
INPUT SENSOR CONFIG
SPT.S
Space Temp Sensor
Enable/Disable
SPTSENS
Disable
SP.O.S
Space Temp Offset Sensor
Enable/Disable
SPTOSENS
Disable
SP.O.R
Space Temp Offset Range
1 - 10
SPTO_RNG
5
RRH.S
Return Air RH Sensor
Enable/Disable
RARHSENS
Disable
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
FLTS_ENA
Disable
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...