APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
GENERAL
Occupied ?
Yes/No
OCCUPIED
forcible
Static Pressure
" H2O
SP
Building Pressure
" H2O
BP
Outside Air Rel.Humidity
%
OARH
forcible
Return Air Rel.Humidity
%
RARH
forcible
Space Temperature Offset
^F
SPTO
forcible
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
Static Pressure Reset
SPRESET
forcible
IAQ - PPM Return CO2
IAQ
forcible
OAQ - PPM Return CO2
OAQ
forcible
IAQ Min.Pos.Override
%
IAQMINOV
forcible
GENERIC
20 points dependent upon
the configuration of the
“generics” table in the
Service-Config section on page 162.
HEATING
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Heat Control Type……:
ascii text strings
Re-Heat Control Type
ascii text strings
Heating Mode………..:
ascii text strings
Current Heat Stage
HT_STAGE
Heating Control Point
dF
HEATCPNT
Heat Relay 1
HS1
Heat Relay 2
HS2
Relay 3 W1 Gas Valve 2
HS3
Relay 4 W2 Gas Valve 2
HS4
Relay 5 W1 Gas Valve 3
HS5
Relay 6 W2 Gas Valve 3
HS6
Heat Interlock Relay
HIR
forcible
Heat Stage 1 Timeguard
HS1_TG
Heat Stage 2 Timeguard
HS2_TG
Heat Stage 3 Timeguard
HS3_TG
Heat Stage 4 Timeguard
HS4_TG
Heat Stage 5 Timeguard
HS5_TG
Heat Stage 6 Timeguard
HS6_TG
HMZR
HVAC Mode………
Ascii text strings
Humidimizer Capacity
0-100
%
HMZRCAPC
Condenser EXV Position
0-100
%
COND_EXV
Bypass EXV Position
0-100
%
BYP_EXV
Humidimizer #-Way Valve
On/Off
HUM3WVAL
Cooling Control Point
–20-140
DF
COOLCPNT
Evaporator Discharge Tmp
–40-240
DF
EDT
Heating Control Point
–20-140
DF
HEATCPNT
Leaving Air Tmp
–40-240
DF
LAT
MODEDISP
System Mode…………:
ascii text strings
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Currently Occupied
On/Off
MODEOCCP
Timed Override in effect
On/Off
MODETOVR
DCV resetting min pos
On/Off
MODEADCV
Supply Air Reset
On/Off
MODESARS
Demand Limit in Effect
On/Off
MODEDMLT
Temp.Compensated Start
On/Off
MODETCST
IAQ pre-occ purge active
On/Off
MODEIQPG
Linkage Active - DAV
On/Off
MODELINK
Mech.Cooling Locked Out
On/Off
MODELOCK
HVAC Mode Numerical Form
number
MODEHVAC
MODETRIP
Unoccup. Cool Mode Start
UCCLSTRT
Unoccup. Cool Mode End
UCCL_END
Occupied Cool Mode Start
OCCLSTRT
Occupied Cool Mode End
OCCL_END
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
Occupied Heat Mode End
OCHT_END
Occupied Heat Mode Start
OCHTSTRT
Unoccup. Heat Mode End
UCHT_END
Unoccup. Heat Mode Start
UCHTSTRT
HVAC Mode…………..:
ascii text strings
string
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...