APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
See legend on page 189.
POINT DESCRIPTION
CCN
POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Power Exhaust Relay B
PE_B
R
n/a
n/a
n/a
BV:73
pe_b_1
Power Exhaust Relay C
PE_C
R
n/a
n/a
n/a
BV:74
pe_c_1
Pressurization Input
PRES
W
n/a
n/a
0-1
BV:1061
smk_press_1
Pull Down Cap Override
PULLDOWN
R
n/a
n/a
n/a
BV:75
pulldown_1
Relay 3 W1 Gas Valve 2
HS3
R
n/a
n/a
n/a
BV:76
hs3_1
Relay 4 W2 Gas Valve 2
HS4
R
n/a
n/a
n/a
BV:77
hs4_1
Relay 5 W1 Gas Valve 3
HS5
R
n/a
n/a
n/a
BV:78
hs5_1
Relay 6 W2 Gas Valve 3
HS6
R
n/a
n/a
n/a
BV:79
hs6_1
Remote Alarm/Aux Relay
ALRM
W
n/a
n/a
0-1
BV:2014
aux_relay_1
Remote Econ. Disabled ?
ECONDISA
R
n/a
n/a
n/a
BV:80
econdisa_1
Remote Economizer Enable
ECONENBL
W
n/a
n/a
0-1
BV:1010
remote_econ_enable_1
Remote Input State
RMTIN
W
n/a
n/a
0-1
BV:81
rmtin_1
Remote Switch Config
RMTINCFG
W
n/a
0
0-3
AV:130
rmtincfg_1
Requested Heat Stage
HT_STAGE
R
n/a
n/a
n/a
AV:2003
heat_run_1
Reset Limit
LIMT
W
°^F
10
0-20
AV:131
limt_1
Reset Ratio
RTIO
W
n/a
2
0-10
AV:132
rtio_1
Return Air Enthalpy
RAE
R
n/a
n/a
n/a
AV:133
rae_1
Return Air Relative Humidity
RARH
W
%
n/a
0-100
AV:134
rarh_1
Return Air Temperature
RAT
W
°F
n/a
-280
AV:135
rat_1
Schedule Number
SCHEDNUM
W
n/a
0
0-99
AV:136
schednum_1
Slow Change Cap Override
SLO_CHNG
R
n/a
n/a
n/a
BV:86
slo_chng_1
Smoke Purge Input
PURG
W
n/a
n/a
0-1
BV:1062
smk_purg_1
Soft Stop Request
SOFTSTOP
W
n/a
n/a
0-1
BV:87
softstop_1
SP Reset Limit
SPRLIMIT
W
n/a
0.75
0-2
AV:143
sprlimit_1
SP Reset Ratio
SPRRATIO
W
n/a
0.2
0-2
AV:144
sprratio_1
Space Temp Offset Range
SPTO_RNG
W
°^F
5
10-Jan
AV:139
spto_rng_1
Space Temperature
SPT
W
°F
n/a
-280
AV:137
spt_1
Space Temperature Offset
SPTO
W
°^F
n/a
-20
AV:138
spto_1
Staged Gas LAT 1
LAT1SGAS
R
°F
n/a
n/a
AV:150
lat1sgas_1
Staged Gas LAT 2
LAT2SGAS
R
°F
n/a
n/a
AV:151
lat2sgas_1
Staged Gas LAT 3
LAT3SGAS
R
°F
n/a
n/a
AV:152
lat3sgas_1
Staged Gas LAT Sum
LAT_SGAS
R
°F
n/a
n/a
AV:153
lat_sgas_1
Staged Gas Limit Sw Temp
LIMSWTMP
R
°F
n/a
n/a
AV:154
limswtmp_1
Startup Delay Time
DELAY
W
sec
0
0-900
AV:155
delay_1
Stat. Pres. Reset Config
SPRSTCFG
W
n/a
0
0-4
AV:156
sprstcfg_1
Static Pressure
SP
R
in H2O
n/a
n/a
AV:1016
static_press_1
Static Pressure Reset
SPRESET
W
n/a
n/a
0-15
AV:157
spreset_1
Static Pressure Setpoint
SPSP
W
in H2O
1.5
0-5
AV:3050
sa_static_stpt_1
Supply Air Reset
MODESARS
R
n/a
n/a
n/a
BV:93
modesars_1
Supply Air Setpnt. Reset
SASPRSET
W
°^F
n/a
0-20
AV:158
sasprset_1
Supply Air Setpoint
SASP
W
°F
55
45-75
AV:3007
sa_temp_stpt_1
Supply Fan not on 30s ?
SFONSTAT
R
n/a
n/a
n/a
BV:22
sfonstat_1
Supply Fan Relay
SFAN_RLY
R
n/a
n/a
n/a
BV:94
sfan_rly_1
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...