189
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
LEGEND
POINT DESCRIPTION
CCN
POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
VAV Occ. Cool Off Delta
VAVOCOFF
W
°^F
2
25-Jan
AV:180
vavocoff_1
VAV Occ. Cool On Delta
VAVOCON
W
°^F
3.5
0-25
AV:181
vavocon_1
VAV Unocc Fan Retry Time
SAMPMINS
W
min
60
0-720
AV:182
sampmins_1
Vent Reheat RAT Offset
DHVRAOFF
W
°^F
0
0-8
AV:183
dhvraoff_1
Vent Reheat Setpoint
DHVHT_SP
W
°F
70
55-95
AV:184
dhvht_sp_1
Vent Reheat Setpt Select
DHVHTCFG
W
n/a
0
0-1
AV:185
dhvhtcfg_1
VFD Fire Speed Override
STATPFSO
W
%
100
0-100
AV:187
statpfso_1
VFD Maximum Speed
STATPMAX
W
%
100
0-100
AV:188
statpmax_1
VFD Minimum Speed
STATPMIN
W
%
20
0-100
AV:189
statpmin_1
VFD/Act. Fire Speed/Pos.
BLDGPFSO
W
%
100
0-100
AV:186
bldgpfso_1
BP
—
Building Pressure
CEM
—
Controls Expansion Module
DAQ
—
Differential Air Quality
DBC
—
Dry Bulb Changeover
DCV
—
Demand Controlled Ventilation
DDBC
—
Differential Dry Bulb Changeover
DEC
—
Differential Enthalpy Changeover
DH
—
Dehumidification
EDT
—
Evaporator Discharge Temperature
IAQ
—
Indoor Air Quality
IGC
—
Integrated Gas Control
LAT
—
Leaving Air Temperature
n/a
—
Not Available
OAEC
—
Outdoor Air Enthalpy Changeover
OAQ
—
Outdoor Air Quality
OAT
—
Outdoor Air Temperature
PID
—
Proportional, Integral, Derivative
R
—
Read
RAT
—
Return Air Temperature
RH
—
Relative Humidity
SASP
—
Supply Air Setpoint
SP
—
Setpoint
SPT
—
Space Temperature
TSTAT
—
Thermostat
VAV
—
Variable Air Volume
VFD
—
Variable Frequency Drive
W
—
Write
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...