APPENDIX C — VFD INFORMATION (cont)
Table B — VFD Configurations
VFD Operation —
The VFD keypad is shown in Fig. B.
The function of SOFT KEYS 1 and 2 change depending on
what is displayed on the screen. The function of SOFT KEY 1
matches the word in the lower left-hand box on the display
screen. The function of SOFT KEY 2 matches the word in the
lower right-hand box on the display screen. If the box is empty,
then the SOFT KEY does not have a function on that specific
screen. The UP and DOWN keys are used to navigate through
the menus. The OFF key is used to turn off the VFD. The
AUTO key is used to change control of the drive to automatic
control. The HAND key is used to change control of the drive
to local (hand held) control. The HELP button is used to access
the help screens.
START UP WITH ASSISTANT — Initial start-up has been
performed at the factory. To start up the VFD with the Start-Up
Assistant or reset the VFD with the Carrier defaults, perform
the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2. Use the UP or DOWN keys to highlight ASSISTANTS
on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight Carrier Assistant
and press SEL (SOFT KEY 2).
4. The Carrier Assistant will ask questions to determine the
correct parameters for the VFD. Select the desired values
and press SAVE (SOFT KEY 2) after every change. The
process will continue until all the parameters are set.
a. The Carrier Assistant will ask “Is this an Air
Handler or Rooftop?” Select “Rooftop.”
b. The Carrier Assistant will ask “Is this a High E or
Premium E motor?” Select the correct efficiency
type.
c. If the VFD can be used with two different size
(HP) motors, then the Carrier Assistant will ask the
user to choose the proper HP. Select the correct
motor horsepower.
START UP BY CHANGING PARAMETERS INDIVIDU-
ALLY — Initial start-up is performed at the factory. To start up
the VFD with by changing individual parameters, perform the
following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2. Use the UP or DOWN keys to highlight PARAMETERS
on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (SOFT KEY 2).
PARAMETER GROUP
PARAMETER TITLE
PARAMETER INDEX
CARRIER DEFAULT
Start-Up Data
LANGUAGE
9901
ENGLISH
APPLIC MACRO
9902
USER 1
MOTOR CTRL MODE
9904
SCALAR: FREQ
MOTOR NOM VOLT
9905
460v
MOTOR NOM CURR
9906
*TBD*
MOTOR NOM FREQ
9907
60 Hz
MOTOR NOM SPEED
9908
1750 rpm
Start/Stop/Dir
EXT1 COMMANDS
1001
DI-1
DIRECTION
1003
REVERSE
Analog Inputs
MINIMUM AI1
1301
20.0 %
MAXIMUM AI1
1302
100.0 %
Relay Outputs
RELAY OUTPUT 1
1401
STARTED
RELAY OUTPUT 2
1402
RUN
RELAY OUTPUT 3
1403
FAULT (-1)
System Controls
RUN ENABLE
1601
NOT SELECTED
START ENABLE 1
1608
DI-4
OVER RIDE
OVERRIDE SEL
1701
DI-3
OVERRIDE FREQ
1702
60 Hz
OVERRIDE SPEED
1703
1750 rpm
OVER PASS CODE
1704
ENTERED
OVERRIDE
1705
ON
STOP FUNCTION
2102
RAMP
Accel/Decel
ACCELER TIME 1
2202
30.0s
DECELER TIME 1
2203
30.0s
MOTOR
SWITCHING FREQ
2606
8 kHz
Fig. B — VFD Keypad
A39-2918
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...