160
APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
ECON
Economizer Installed ?
Yes/No
ECON_ENA
Yes
Economizer Min.Position
0 - 100
%
ECONOMIN
20
Economizer Max.Position
0 - 100
%
ECONOMAX
98
Econ Pos at Min VFD Spd
0 - 100
%
EPOSMNFS
5
Econ Pos at Max VFD Spd
0 - 100
%
EPOSMXFS
5
Economzr trim for sumZ ?
Yes/No
ECONTRIM
Yes
Econ ChangeOver Select
0 - 3
ECON_SEL
1
OA Enthalpy ChgOvr Selct
1 - 5
OAEC_SEL
2
Outdr.Enth Compare Value
18 - 32
OAEN_CFG
24
High OAT Lockout Temp
55 - 120
dF
OAT_LOCK
60
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
Economizer Control Type
1-3
ECON_CTL
1
Economizer Switch Config
0-2
ECOSWCFG
0
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
Unoc Econ Free Cool Time
0-720
min
UEFCTIME
120
Un.Ec.Free Cool OAT Lock
40-70
dF
UEFCNTLO
50
T24_CFG
Economizer Installed ?
Yes/No
ECON_ENA
Yes
SAT Settling Time
secs
SAT_SET
240
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
Log Title 24 Faults
Yes/No
T24LOGFL
No
T24 Econ Move Detect
T24ECMDB
1
T24 Econ Move SAT Test
T24ECSTS
10
T24 Econ Move SAT Change
T24SATMD
0.2
T24 Econ RAT-OAT Diff
T24RATDF
15
T24 Heat/Cool End Delay
T24CHDLY
25
T24 Test Minimum Pos.
T24TSTMN
15
T24 Test Maximum Pos.
T24TSTMX
85
EDTR
EDT Reset Configuration
0 - 3
EDRSTCFG
0
Reset Ratio
0 - 10
RTIO
2
Reset Limit
0 - 20
^F
LIMT
10
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
HEAT
Heating Control Type
0 - 4
HEATTYPE
0
Heating Supply Air Setpt
80-120
dF
SASPHEAT
85
Occupied Heating Enabled
Yes/No
HTOCCENA
No
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
Fan-off Delay, Gas Heat
45-600
GAS_FOD
45
Fan-off Delay, Elec Heat
10-600
ELEC_FOD
30
Staged Gas Heat Type
0 - 4
HTSTGTYP
0
Max Cap Change per Cycle
5 - 45
HTCAPMAX
45
S.Gas DB min.dF/PID Rate
0 - 5
HT_MR_DB
0.5
St.Gas Temp. Dead Band
0 - 5
^F
HT_SG_DB
2
Heat Rise dF/sec Clamp
0.05 - 0.2
HTSGRISE
0.06
LAT Limit Config
0 - 20
^F
HTLATLIM
10
Heat Control Prop. Gain
0 - 1.5
HT_PGAIN
1
Heat Control Derv. Gain
0 - 1.5
HT_DGAIN
1
Heat PID Rate Config
60 - 300
sec
HTSGPIDR
90
IAQ_
Economizer Min.Position
0 - 100
%
ECONOMIN
5
Econ Pos at Min VFD Spd
0 - 100
%
EPOSMNFS
5
Econ Pos at Max VFD Spd
0 - 100
%
EPOSMXFS
5
IAQ Demand Vent Min.Pos.
0 - 100
%
IAQMINP
0
IAQ Analog Sensor Config
0 - 4
IAQANCFG
0
IAQ 4-20 ma Fan Config
0 - 2
IAQANFAN
0
IAQ Discrete Input Config
0 - 2
IAQINCFG
0
IAQ Disc.In. Fan Config
0 - 2
IAQINFAN
0
OAQ 4-20ma Sensor Config
0 - 2
OAQANCFG
0
IAQ Econo Override Pos.
0 - 100
%
IAQOVPOS
100
Diff.Air Quality LoLimit
0 - 1000
DAQ_LOW
100
Diff. Air Quality HiLimit
100 - 2000
DAQ_HIGH
700
DAQ PPM Fan Off Setpoint
0 - 2000
DAQFNOFF
200
DAQ PPM Fan On Setpoint
0 - 2000
DAQFNON
400
Diff. AQ Responsiveness
–5 - 5
IAQREACT
0
OAQ Lockout Value
0 - 2000
OAQLOCK
0
User determined OAQ
0-5000
OAQ_USER
400
IAQ Low Reference
0 - 5000
IAQREFL
0
IAQ High Reference
0 - 5000
IAQREFH
2000
OAQ Low Reference
0 - 5000
OAQREFL
0
OAQ High Reference
0 - 5000
OAQREFH
2000
IAQ Purge
Yes/No
IAQPURGE
No
IAQ Purge Duration
5-60
min
IAQPTIME
15
IAQ Purge LoTemp Min Pos
0-100
%
IAQPLTMP
10
IAQ Purge HiTemp Min Pos
0-100
%
IAQPHTMP
35
IAQ Purge OAT Lockout
35-70
dF
IAQPNTLO
50
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...