10
A. Vent Guidelines Due to Removal of an
Existing Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to
be too large for proper venting of the remaining
appliances. At the time of removal of an existing boiler,
the following steps shall be followed with each appli-
ance remaining connected to the common venting
system placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation:
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no block-
age or restriction, leakage, corrosion, and other
defi ciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust fans, such as range-hoods and
bathroom exhausts, so they will operate at maxi mum
speed. Do not operate a summer exhaust fan. Close
fi replace dampers.
4. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions.
Adjust thermo stat so appliance will operate continu-
ously.
5. Test for spillage at the draft hood relief opening after
fi ve (5) minutes of main burner operation. Use the
fl ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remain ing connected to the common venting system
properly vents when tested as outlined above, return
doors, win dows, exhaust fans, fi replace dampers and
any other gas burning appliance to their previous
conditions of use.
Table 4: Vent/Air Intake Length
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the
National Fuel Gas Code
, NFPA
54/ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part II in the
National Fuel Gas Code
, NFPA 54/
ANSI Z223.1.
B. General Guidelines
1. Vent system installation must be in accordance with
National Fuel Gas Code
, NFPA 54/ANSI Z221.3 or
applicable provisions of local building codes.
Contact local building or fi re offi cials about restric-
tions and installation inspection in your area.
2. The Revolution is designed to be installed as either a
Direct Vent boiler or Power Vent boiler. In the
Direct Vent confi guration all of the air for combus-
tion is supplied directly to the burner enclosure from
outdoors and fl ue gases are vented directly outdoors
(through wall or roof). In the Power Vent confi gura-
tion, room air provides air for combustion and
ventilation. Flue gases are still vented directly
outdoors (through wall or roof).
Note: Venting requirements change if indoor air is
used.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper confi guration of
venting system. See Table 1.
4. This appliance requires a Special Gas Vent. The
product is designed to use Burnham supplied
AL 29-4C
®
Stainless Steel vent system components.
The following manufacturers offer similar
AL 29-4C
®
components and are approved for use
with this product: Heat-Fab Inc. - Saf-T-Vent, Flex-
L International Inc. - Star-34, Z-Flex U. S., Inc. -
Z-Vent, and Protech Systems , Inc.- FasNSeal™.
The use of these alternate manufacturer’s venting
systems will require adapters to connect to the
Burnham supplied vent connector and vent terminal.
These adapters are not supplied with this unit and
should be obtained from the supplier of the alternate
manufacturer’s venting system. See Table 3 for
complete list of Burnham Vent System Components.
l
e
d
o
M
e
p
i
P
e
k
a
t
n
I
r
i
A
"
3
)
.
t
F
.
v
i
u
q
E
(
e
p
i
P
e
k
a
t
n
I
r
i
A
"
4
)
.
t
F
.
v
i
u
q
E
(
e
p
i
P
t
n
e
V
"
3
)
.
t
F
.
v
i
u
q
E
(
.
n
i
M
.
x
a
M
.
n
i
M
.
x
a
M
.
n
i
M
.
x
a
M
4
V
R
&
3
V
R
0
1
2
5
-
-
-
-
-
-
-
-
-
-
8
0
5
7
V
R
&
6
V
R
,
5
V
R
-
-
-
-
-
-
-
-
-
-
0
1
2
5
Содержание Burnham Hydronics Revolution RV3
Страница 5: ...5 Figure 2 Dimensions...
Страница 15: ...15 Figure 4 Recommended Separate Horizontal Vent Air Intake Installation...
Страница 16: ...16 Figure 5 Separate Horizontal Vent Air Intake Terminal Confi guration...
Страница 19: ...19 Figure 7 Attic Offset Figure 6 Vertical Vent Installation...
Страница 21: ...21 Figure 9 Vertical Air Intake Piping...
Страница 24: ...24 Figure 10 Combination Horizontal Vent Air Installation...
Страница 25: ...25 Figure 11 Combination Horizontal Vent Air Terminal Installation...
Страница 30: ...30 Figure 13 Combination Vertical Air Intake Terminal Assembly...
Страница 31: ...31 Figure 14 Combination Vertical Vent Disc Terminal Assembly...
Страница 34: ...34 Figure 15 Indoor Air Horizontal Vent Installation...
Страница 35: ...35 Figure 16 Indoor Air Vertical Vent Installation...
Страница 37: ...37 Figure 19 Indoor Air Air Intake Terminal Installation...
Страница 46: ...46 Figure 28 Recommended Boiler Piping For Circulator Zoned Heating Systems...
Страница 47: ...47 Figure 29 Boiler Piping for Zone Valve Zoned Systems...
Страница 52: ...52 Figure 31 Internal Boiler Wiring Schematic Diagram...
Страница 56: ...56 Figure 33 Single Heating Zone Only Wiring Schematic...
Страница 58: ...58 Figure 35 Circulator Zoned System Wiring Schematic...
Страница 59: ...59 Figure 36 Zone Valve Zoned System Wiring Schematic...
Страница 60: ...60 Figure 37 Zone Valve Zoned System Wiring Schematic...
Страница 61: ...61 Figure 38 Different Manufacturer s Zone Valve Connections to Honeywell R8889...
Страница 62: ...62 Figure 39 Circulator Zoning with EC5000 Wiring Schematic...
Страница 63: ...63 Figure 40 Zone Valve Zoning with EC5000 Wiring Schematic...
Страница 64: ...64 Figure 41 Radiant Floor Circulator Zoned System with Alliance Water Heater...
Страница 65: ...65 Figure 42 Radiant Floor Zone Valve Zoned System with Alliance Water Heater...
Страница 68: ...68 Figure 43 Modular Boiler Piping...
Страница 69: ...69 Figure 44 Alternate Modular Boiler Piping...
Страница 71: ...71 Figure 45 Operating Instructions...
Страница 74: ...74 Figure 49 Variable Speed Control Sequence of Operation Figure 50 Internal Primary Secondary Piping...
Страница 77: ...77 Figure 53 Cleaning Boiler Flue Passages...
Страница 80: ...80 Revolution Troubleshooting Tree...
Страница 81: ...81 Revolution Troubleshooting Tree...
Страница 84: ...84...
Страница 86: ...86...
Страница 88: ...88...
Страница 90: ...90...
Страница 92: ...92...
Страница 95: ...95 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 96: ...96 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 97: ...97 SERVICE RECORD DATE SERVICE PERFORMED...