4.5
24 V supply voltage (DC)
Note
The negative terminal of the supply voltage is
not
connected to
PE in the AC-DC module. Grounding must be performed by the
customer, as close to the housing as possible.
24 V supply voltage (DC)
Fig. 17
■
At the AC-DC module: Phoenix PCB plug connector
■
Required counterpart: 2-pin connector, 16A, GMSTB 2.5
HCV/ 2-ST-7.62-LR
■
2 x 1.5 mm
2
/ 2 x AWG 16
The 24V supply voltage is necessary for supplying the following
components of the AC-DC module:
■
Control
■
Fan
■
Driver of power stages
4.6
Communication interfaces
Communication interfaces
Fig. 18
■
RJ-45
■
Twisted pair patch cable in accordance with standard TIA/
EIA-568A/B
■
CAT 5 or higher
■
Max. length: 100 m
A67-0141-00.BKEN-
001-05
2020-06-10
Interfaces
25
View
Connection
Cable requirement
Use
View
Connection
Cable requirement
Содержание TruConvert AC 3025
Страница 1: ...Operator s manual TruConvert AC 3025 TruConvert System Control...
Страница 2: ......
Страница 6: ...II Good to know 2020 06 10 A67 0141 00 BKEN 001 05...