Addr
Description
Unit
Res
olu-
tion
Default
Min
Max
Dat
atyp
e
Typ
e
Len
gth
FCr
FCw
4306
0 = power distribution, 1
= current distribution, 2 =
auto
-
1.0
2
0
2
UIN
T16
Regi
ster
1
03
06
ActualValues
5000
State of device: 0 =
Power up, 1 = Alarm, 2
= Idle, 3 = Operation, 4
= Maintenance
-
1.0
-1
-2
10
INT
16
Regi
ster
1
04
5001
Number of connected
slave modules
cnt
1.0
0
16
UIN
T16
Regi
ster
1
04
5002
Number of connected
sub slave modules
cnt
1.0
0
0
5
UIN
T16
Regi
ster
1
04
5020
Nominal grid frequency
Hz
0.1
500
UIN
T16
Regi
ster
1
04
5021
Nominal grid voltage
V
1.0
400
UIN
T16
Regi
ster
1
04
5022
Nominal apparent power
capability
VA
1.0
25000
UIN
T16
Regi
ster
1
04
5023
Actvie grid type:
0 = grid-tied, 400V, 50Hz
1 = grid-tied, 480V, 60Hz
2 = island mode, 400V,
50Hz
3 = island mode, 480V,
60Hz
4 = grid-tied, 380V, 60Hz
-
1.0
0
0
1
UIN
T16
Regi
ster
1
04
5130
Apparent power L1
kVA
0.00
1
0
UIN
T16
Regi
ster
1
04
5131
Apparent power L2
kVA
0.00
1
0
UIN
T16
Regi
ster
1
04
5132
Apparent power L3
kVA
0.00
1
0
UIN
T16
Regi
ster
1
04
5133
Overload capacity L1
%
0.1
0
0
100
0
UIN
T16
Regi
ster
1
04
5134
Overload capacity L2
%
0.1
0
0
100
0
UIN
T16
Regi
ster
1
04
5135
Overload capacity L3
%
0.1
0
0
100
0
UIN
T16
Regi
ster
1
04
5140
Active power L1
kW
0.00
1
INT
16
Regi
ster
1
04
5141
Active power L2
kW
0.00
1
INT
16
Regi
ster
1
04
5142
Active power L3
kW
0.00
1
INT
16
Regi
ster
1
04
5150
Grid current RMS L1
A
0.01
0
880
0
UIN
T16
Regi
ster
1
04
5151
Grid current RMS L2
A
0.01
0
880
0
UIN
T16
Regi
ster
1
04
A67-0141-00.BKEN-
001-05
2020-06-10
Operation
53