Addr
Description
Unit
Res
olu-
tion
Default
Min
Max
Dat
atyp
e
Typ
e
Len
gth
FCr
FCw
1018
Setting for connected sys-
tem configuration:
No config = 0,
Simulator = 1,
DC-DC only = 2,
n*AC-DC m*DC-DC = 3
-
1.0
0
0
6
UIN
T16
Regi
ster
1
03
06
1028
Variable to save or reset
customer values:
1: save parameter
-1: restore default settings
-
1.0
0
-1
1
INT
16
Regi
ster
1
03
06
Information system
2000
Serial number system
control
Strin
g
UIN
T32
Regi
ster
2
04
16
2008
Serial number AC-DC
module
-
1.0
0
UIN
T32
Regi
ster
2
03
16
Nominal values
4000
Power stage configuration:
1 = power stage on
0 = power stage off
-
1.0
0
0
1
UIN
T16
Coil
1
01
05
4001
Configuration nominal val-
ues AC for phases L1 -
L3:
1 = symmetric
0 = asymmetric (individ-
ual configuration possible)
-
1.0
1
0
1
UIN
T16
Coil
1
01
05
4002
Resets current alarm and
warning messages
-
1.0
0
0
1
UIN
T16
Coil
1
01
05
4005
Precharge DC link config-
uration:
0 = device waits for exter-
nal precharge of DC link
1 = device precharges
external DC link to neces-
sary start-up voltage
2 = behaviour similar to
1 with additional support
of DC submodules (nec-
essary for island opera-
tion)
-
1.0
1
0
2
UIN
T16
Regi
ster
1
03
06
4006
Sets reference frame con-
vention (0 = producer ref-
erence frame; 1 = con-
sumer reference frame)
-
1.0
0
0
1
UIN
T16
Regi
ster
1
03
06
4007
Specifies the slave that
will be addressed (0 =
broadcast / same values
for all slaves)
-
1.0
0
0
16
UIN
T16
Regi
ster
1
03
06
50
Operation
2020-06-10
A67-0141-00.BKEN-
001-05