Trine 4100 Electric Strike Скачать руководство пользователя страница 63

1440 Ferris Place  

  Bronx  

  New York  

  10461

Tel. No. (718) 829-2332  

  Fax No. (718) 829-6405

Website: www.TrineOnline.com

4

TROUBLESHOOTING GUIDE SECTION:

The 017TDC-2 & 3 and the 018-2 operates on radio frequency (RF) signaling and may have some problems being installed in certain 
locations. Radio frequency (RF) signals are similar in principle as two people conversing. RF communications however are more difficult to 
troubleshoot because RF modulates at frequencies that are not audible to human ears. 

Let's say that you and I are comfortably conversing, if a person starts talking loud next to us, then we may start to automatically go closer 
and closer to each other until we can once again understand each other.

RF devices will work the same way. The first objective in troubleshooting is to spot the troublemaker, in this case the offending device. The 
offending device can be one or the combination of the following items: light dimmers, fluorescent lights, TV or computer CRT displays and 
any piece of equipment using a switching power supply or "clock" oscillator (computers and other digital devices). Additionally, ham and CB 
transmitters, remote controls, wireless phones, cellular phones, commercial taxi/police/aircraft radios, microwave ovens, motion sensors, 
radar systems, and a myriad of medical and industrial RF devices.

As you can appreciate from the litany of devices above almost any perimeter can have multiple sources of RF noisemakers. Deciding the 
final position for mounting the 017TDC will immensely improve your chances of installation success. Before nailing the 017TDC receiver 
down, choose an initial location and use a 10 feet electrical cord and walk test the 017TDC's sensitivity to receive the 018-2's signal. Once 
you have determine the most ideal spot, that is the place you will install the receiver.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Transmitter does not work
(LED lamp does not light)

Transmitter does not work
(LED lamp turns ON)

Receiver does not work

Receiver works intermittently

Battery is low

Battery is not properly installed 

Transmitter is out of range 

Wiring connections may be faulty 

Security Code mismatch 

Wiring connection may be faulty 

RF interference 

Security Code mismatch 

Faulty power supply 

Loose wiring connections or shorted wire 

Replace the battery. Use an A23 size 12VDC Alkaline battery.

Reinstall the battery correctly (see battery polarity drawing above)

Move the transmitter closer to the receiver (see above article)

Check your wiring against the appropriate wiring scheme on page 1, 2 & 3 

See if your receiver and transmitter security code match (see page 3) 

Check your wiring against the appropriate wiring scheme on page 1, 2 & 3  

Read the article above regarding RF interference 

See if your receiver and transmitter security code match (see page 3) 

Check the power supply for correctness of voltage and capacity 

Carefully check all your wiring connections and tighten loose connections 

017TDC-3 SWITCHING MODE SETTING

:

The 017TDC-3 has two relays capable of being triggered together by one button from the 018-2 transmitter or separately by the two buttons from the 018-2 
transmitter. Set the relay control switch to your desire mode but following the coding below. 

NOTE: 

The 017TDC-2 has only one relay 
and is triggered by any of the two 
buttons on the 018-2 transmitter. 

017TDC-3

RELAY CONTROL

SWITCH

RELAY

CHANNEL

1  2  1  2

A  A  B  B

"A" BUTTON OPERATES "1" RELAY
"B" BUTTON OPERATES "2" RELAY

RELAY

CHANNEL

1  2  1  2

A  A  B  B

ALL CHANNELS "OFF"

RELAY

CHANNEL

1  2  1  2

A  A  B  B

"A" BUTTON OPERATES BOTH RELAYS

RELAY

CHANNEL

1  2  1  2

A  A  B  B

"B" BUTTON OPERATES
BOTH RELAYS

RELAY

CHANNEL

1  2  1  2

A  A  B  B

ANY BUTTON OPERATES
BOTH RELAYS

+

-

+

-

USE  

A23 12VDC

 

ALKALINE BATTERY OR IT'S 

FOLLOWING EQUIVALENT:

 MN21, GP23AE, A23, 

VA23GA, MS21

BATTERY SPECIFICATION

AND ORIENTATION:

NEGATIVE

SIDE

POSITIVE

SIDE

FCC ID: PFO018-2

018-2 TRANSMITTER

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following two conditions: (1) this 

device may not cause harmful interference and (2) this device 

must accept any interference received, including interference 

that may cause undesired operation.

NOTICE REGARDING THE 018-2 TRANSMITTER

Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, 
including interference that may cause undesired operation of the device

Содержание 4100 Electric Strike

Страница 1: ...rike position if possible 5 Correct excessive warping of door USING THE LATCH SPACER SHIMS CONTINUED For locks not aligning to the vertical center of the strike mount the shims as shown below Most if...

Страница 2: ...nnect socket to the power wires coming out of the frame 5 Connect the strikes bottom terminal to the quick connect socket 6 Tuck the wires inside the door frame 7 Install the electric strike into the...

Страница 3: ...s 50 Ohms 24AC 50 60Hz 420 Amps 10 08 Watts 50 Ohms 4200 ELECTRICAL CHARACTERISTICS OPERATING TEMP RANGE 20 C TO 40 C DO NOT APPLY A VOLTAGE OF MORE THAN 10 OVER THE RATED OPERATING VOLTAGE OF THE STR...

Страница 4: ...ON FACEPLATE DIMENSIONS Metal Frame TAB DIMENSIONS Wood Frame Use 12 24 x 1 2 inch Philips Mounting Screws for tab holes Aluminum Frame MOUNTING TABS 2 SUPPLIED 4 7 8 1 17 64 4 1 8 3 3 8 1 1 16 8 1 16...

Страница 5: ...power ONLY as the last step 3 Carefully choose the quick connect socket to match the required voltage The quick connect sockets are labeled 12VDC Blue Wire or 24VDC White Wire 4 Use the crimp connecto...

Страница 6: ...or 4 Adjust electric strike position if possible 5 Correct excessive warping of door PHONE 718 829 2332 FAX 718 829 6405 1440 FERRIS PLACE BRONX NY 10461 email customerservice trineonline com website...

Страница 7: ...WITCH NORMALLY CLOSED FAIL SAFE CONFIGURED STRIKE USE 12V THRU 24V AC OR DC TRANSFORMER TO 120V AC LINE WIRING FOR FAIL SAFE MODE WITH OPTIONAL BUZZER SWITCH SINGLE POLE DOUBLE THROW FAIL SAFE CONFIGU...

Страница 8: ...WITCH NORMALLY CLOSED FAIL SAFE CONFIGURED STRIKE USE 12V THRU 24V AC OR DC TRANSFORMER TO 120V AC LINE WIRING FOR FAIL SAFE MODE WITH OPTIONAL BUZZER SWITCH SINGLE POLE DOUBLE THROW FAIL SAFE CONFIGU...

Страница 9: ...le the 4850 is unlatched swing the door open If the door opens then the bolt maybe applying pressure to the latch Adjust the position of the 4850 to relieve the pressure POSSIBLE REMEDIES 1 Re adjust...

Страница 10: ...Push the anchor pins in the back of any 4850 series strike if you desire to use this Figure 5 Crimp the quick connect socket assembly to the power wires Crimp Connectors Quick Connect Socket Assembly...

Страница 11: ...tch cavity Having the latch on center will ensure that the sensor will have enough surface to detect You can use the 1 8 and 1 4 spacer included 1 4 is for 4850LB only to move the 4850LB 4800FLB close...

Страница 12: ...RELAY PANEL INDICATOR OR OTHER SIGNALING DEVICE POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 3 CONTROL PANEL PANEL SIDE WIRING FRAME SIDE WIRING Hook up to either Normally Open or Normally Closed Termin...

Страница 13: ...Solid Cast Latch Stainless Steel Cavity Width 5 8 Height 1 1 8 Depth 1 2 Non handed Heavy duty latch spring Silent Operation Intermittent Duty with the Standard versions Intermittent and Continuous D...

Страница 14: ...ubricating these units will actually hamper their performance by attracting dust and debris into the tight tolerance precision Micro Solenoid assembly GETTING STARTED Before proceeding with your insta...

Страница 15: ...ed to as Silent Operating unlike some types of AC electric releases which make a buzzing sound when activated For some applications such as entrances into apartment buildings or storerooms an audible...

Страница 16: ...16 1 1 32 1 1 4 3 1 8 1 1 8 1 5 16 9 16 3 32 5 16 1 OPTIONAL 1 16 THICK SHIM Page 4 4 7 8 1 1 4 1 7 8 1 1 32 1 11 16 1 3 32 4 1 8 3 4 3 11 32 5 8 3 8 OPTIONAL 1 16 THICK SHIM 1 1 4 4 7 8 3 32 1 1 16...

Страница 17: ...he 3234 s 2 3 4 x 1 1 4 faceplate requires the least amount of jamb preparation when compared with other electric strikes WIRING DIAGRAM 24V DC OR 12V DC TRANSFORMER OPTIONAL BUZZER BZ 12 or BZ 24 TO...

Страница 18: ...serviceable part Note that intermittent coils can only receive power for 1 minute or less 3 If voltage IS NOT present Verify Circuit breaker is on Verify voltage at the transformer power supply output...

Страница 19: ...power to the receptacle into which you will plug your transformer power supply This will enable you to safely cut power during installation and permit troubleshooting if required 5 Verify that the rec...

Страница 20: ...must remain UNLOCKED for extended periods or when required by code The TRINE LC version of MODEL 3258 3458 3258RS and 3458RS can be used for INTERMITTENT DUTY AND CONTINUOUS DUTY ELECTRICAL If you ar...

Страница 21: ...a buzzing sound is distracting or disturbing Verify with your client which they require and if an audible signal when the electric release is activated is desirable then add a audible visual annunciat...

Страница 22: ...AC TRANSFORMER PUSH BUTTON NORMALLY OPEN The rectifier can be positioned before of after the push button in the circuit The LC module can ONLY be positioned after the push button as shown above The L...

Страница 23: ...8 2 7 16 5 8 13 16 2 1 8 1 11 16 1 1 32 1 11 16 1 1 8 ALUMINUM FRAME INSTALLATION The 3458 s 4 5 8 x 1 9 16 full lip steel faceplate requires the least amount of jamb preparation when compared with ot...

Страница 24: ...maged wiring or bad wire splices SYMPTOM Door will not open but strike is working Check for other locks on door Check for proper lock latch engagement SEE SECTION CONFIRMING PROPER LOCK LATCH ENGAGEME...

Страница 25: ......

Страница 26: ...s 2 12 24 x 1 2 EN MTS 14 Shim Kit 3 1 16 Shim EN UNV SHIM 15 Shim Screws 2 6 32 x 1 4 EN SHIM SCR S 16 Shim Screws 2 6 32 x 3 8 EN SHIM SCR L Figure 1 EN400 Electric Strike NOTE Number in parenthesis...

Страница 27: ...all the pivot holes lines up Assemble the Solenoid and secure it with the solenoid Screw as shown Finish the assembly by installing the Cover and securing it with the two assembly Screws Assemble the...

Страница 28: ...the or BLACK negative side wire terminal to the negative side of the circuit RED BLACK INSTALLATION PROCEDURE For new or replacement installation in wood or metal jambs 1 Verify that voltage rating of...

Страница 29: ...releases and that there is sufficient Spring tension to push it to closed positionwhen released If Latch does not have Spring tension disassemble Electric Strike and inspect for improperly installed...

Страница 30: ...icates part in Parts List UL LISTED 10B fire rated class A 3 hour Single Swing Doors UL LISTED 1034 Burglary Resistant Locking Mechanism for Indoor or Outdoor Use ANSI BHMA A156 5 1992 4 7 8 X 1 1 4 F...

Страница 31: ...e to fail safe when replaced with special order part EN SLR RS When using the fail safe Slider a DC Coil must be used The fail safe Slider is identified by the small dimple below the welded tip CHANGI...

Страница 32: ...be employed ELECTRICAL CHARACTERISTICS CHART FAIL SECURE Intermittent Duty NORMALLY LOCKED VOLTAGE CURRENT AMPS OHMS SOUND DUTY 12 VAC 70 4 5 Buzz Intm 24 VAC 37 18 0 Buzz Intm 12 VDC 28 43 0 Silent...

Страница 33: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 34: ...Figure 1 EN800 Electric Strike NOT PART OF ASSEMBLY USED ONLY DURING DISASSEMBLY OR CHANGING FAIL SECURE ACTION UNLESS OTHERWISE SPECIFIED FRAME IS SUPPLIED AS SATIN STAINLESS STEEL US32D SPECIFY OTHE...

Страница 35: ...The EN Electric Strike must be installed with coil assembly up wiring toward top of unit In this position the Electric Strike will be locked without power Fail Secure or locked with power Fail Safe ac...

Страница 36: ...AGE CURRENT AMPS OHMS SOUND DUTY 12VAC 70 4 5 Buzz Intermittent 24VAC 37 18 0 Buzz Intermittent 12VDC 28 43 0 Silent Inter Cont 24VDC 15 164 0 Silent Inter Cont 4 If required run new wiring to door fr...

Страница 37: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 38: ...7 Frame EN 9 FR 8 Assembly Pin EN ASS PN 9 Spring EN SPR 10 Latch Pivot Shaft EN LCH PV ST 11 Guard EN GRD 12 Plastic Cap EN PLC 13 Support Plate EN 9 SP 14 Mounting Screws 2 12 24 1 2 EN MTS 15 Shim...

Страница 39: ...E The EN Electric Strike must be installed with coil assembly up wiring toward top of unit In this position the Electric Strike will be locked without power Fail Secure or locked with power Fail Safe...

Страница 40: ...AGE CURRENT AMPS OHMS SOUND DUTY 12VAC 70 4 5 Buzz Intermittent 24VAC 37 18 0 Buzz Intermittent 12VDC 28 43 0 Silent Inter Cont 24VDC 15 164 0 Silent Inter Cont 4 If required run new wiring to door fr...

Страница 41: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 42: ...t go into slots Fail Safe Indication Back Case 2 Insert assembly pin provided to remove latch pin latch Note The slider should fall thru the strike body after latch is removed remove slider slider gua...

Страница 43: ...r as shown Replace back cover Replace 2 screws and tighten 9 Replacing coil assembly Note Slider must be in position between brackets of coil assembly Note Position wires thru slot toward front of the...

Страница 44: ...n provided to remove latch pin latch Note The slider should fall thru the strike body after latch is removed remove slider slider guard 3 To change the action remove the slider from the frame and reve...

Страница 45: ...e sure slider is free to move up down with no resistance 12 Thread wires thru cover as shown Replace back cover Replace two 1 8 screws and tighten 10 Replacing coil assembly Note Slider must be in pos...

Страница 46: ...k up to either Normally Open or Normally Closed Terminal EN400 EN800 EN850 EN950 EN960 LBSM WIRING SCHEMATIC SWITCHED POWER CONSTANT POWER FIVE WIRE SCHEMATIC UTILIZING ONE TRANSFORMER This wiring arr...

Страница 47: ...DULE CONSTANT POWER 1440 Ferris Place Bronx New York 10461 SIX WIRE SCHEMATIC UTILIZING TWO TRANSFORMERS This wiring arrangement is used to isolate the strike operation from the LB and or the SLIDER s...

Страница 48: ...about approved installation procedures Contact rating 10 Amps at 120 volts 5 Amps at 250 volts DO NOT EXCEED CONTACT RATING CONTENTS 1 UL CSA listed switch 1 Faceplate 2 Wire leads UL Listed w Connect...

Страница 49: ...if used Insulate all connections with wire nuts or tape approved by local codes The door switch can be mounted to the switch case with the 2 flat head screws supplied In the event that the light stays...

Страница 50: ...ing 5 Battery compartment BATTERY INSTALLATION This unit operates on 3VDC batteries using 2 pieces UM 2 size C 1 5V R14 batteries or equivalent Press and slide out the battery door insert batteries in...

Страница 51: ...t 2b Fix Move away from concrete 3a Possible Cause Chime Transmitter are installed too far apart over 100 feet 3b Fix relocate pieces closer to one another C Problem Chime sounds when not intended 1 P...

Страница 52: ...t 2b Fix Move away from concrete 3a Possible Cause Chime Transmitter are installed too far apart over 100 feet 3b Fix relocate pieces closer to one another C Problem Chime sounds when not intended 1 P...

Страница 53: ...ompartment polarity may damagethe unit FEATURES 1 Easy installation 2 Audible alarm for doors windows 3 105dB instant alarm 4 LR44 battery 3 pcs Check that the batteries are installed with correct pol...

Страница 54: ...n the battery becomes weak then it s time to replace the batteries If the unit functions abnormally first check the battery and replace as required The unit is composed of two parts the audible transm...

Страница 55: ...61 3699 PH 718 829 2332 FAX 718 829 6405 E mail customerservice trineonline com www trineonline com 230 8 Note 231 2 Note Push Button Instructions Expand Your Wireless Chime System The 2 note 231 8 no...

Страница 56: ...sh button and chime codes are the same Check orientation of push button battery Check charge of push button and chime batteries replace if necessary Batteries seem OK but the chime doesn t work when i...

Страница 57: ...might require the use of tweezers to remove and replace the jumpers ONE YEAR LIMITED WARRANTY TRINE ACCESS TECHNOLOGY reserves the right to discontin ue and to change specifications at any time witho...

Страница 58: ...s Dong one note and Ding Dong two note The factory setting is for the Ding Dong tune This tune can be changed by following the instructions below Dong one note tune Push button Add jumper to location...

Страница 59: ...s to mount base to wall 5 Connect wires to terminal screws marked Front Transformer and Rear on the chime base 6 Place chime cover securely over the base NOTE FOR LOUDER SOUNDING CHIME PERFORMANCE A 2...

Страница 60: ...w radiant receiver SPECIFICATIONS 1 BOTH PUSH BUTTONS ON THE 018 2 WILL TRIGGER THE 017TDC 2 The 017TDC 2 3 will work with a range of operating voltages These voltages are from 12 Volts through 30 Vol...

Страница 61: ...ITCHES FIGURE 4 TRANSFORMER For DC ONLY For DC ONLY For DC ONLY For DC ONLY Power Supply 12 30 V AC DC Fail Secure Strike 1 Fail Secure Strike 2 USE THE COPPER SHUNT INCLUDED TO SUPPLY POWER TO THE ST...

Страница 62: ...e receiver and the 018 2 transmitter SECURITY CODE SWITCHES FIGURE 8 EXAMPLE CODE SETTING MUST BE THE SAME SWITCH COMBINATION FIGURE 9 FIGURE 10 TIME DELAY KNOBS 017TDC 2 017TDC 3 3 Optionally you can...

Страница 63: ...ections may be faulty Security Code mismatch Wiring connection may be faulty RF interference Security Code mismatch Faulty power supply Loose wiring connections or shorted wire Replace the battery Use...

Страница 64: ...sen the transmitter s assembly screw and snap the front cover open Match the coding of the receiver Figure 1 below shows the location of the DIP switches for the 017TDC 2 3 receiver and the 018 2 tran...

Страница 65: ...hances of installation success Before screwing the 017TDC receiver down choose an initial location and use a 10 feet electrical cord and walk test the 017TDC s sensitivity to receive the 018 2 s signa...

Отзывы: