Door lockset is not
1.
Centerline of lockset not
Check for proper cutout installation of Electric Strike by
secured by Electric
properly aligned to centerline
referring to template and door frame and lockset position.
Strike
of Electric Strike.
2.
Latch does not project
Check for excessive gap between door and jamb.
properly into cavity of
Electric Strike.
Check that lockset is compatible with EN series cavity
and requirements. If necessary, use other type of lockset or
Electric Strike (refer to Trine Catalog for more information).
3.
Latch Spring broken or
Hold Electric Strike so that wiring faces down and apply
missing.
pressure to Latch. Verify that Latch releases and that there is
sufficient Spring tension to push it to closed positionwhen released.
If Latch does not have Spring tension, disassemble Electric Strike
and inspect for improperly installed or broken Spring.
Electric Strike does
1.
Wiring to Electric Strike
Check that electrical connections are secure and that no fraying
not energize
open or shorted.
has occurred during installation. Use voltmeter to verify that
Electric Strike is receiving energizing voltage and that wiring is
not shorted.
2.
Insufficient voltage to
Verify that voltage rating on Electric Strike label is compatible
Electric Strike.
with voltage from secondary transformer (12V or 24V). If
voltages do not match, either replace transformer or change
Electric Strike or Coil Assembly.
Use voltmeter to verify that Electric Strike is receiving proper
voltage and that wiring is not shorted.
If voltage is too low because wire size is too small for length or
wiring to Electric Strike (see wiring-length data on previous page),
either replace wiring or use transformer with higher VA rating.
3.
Slider does not move when
Using an OHM meter, verify that resistance of the Coils matches
Coil receives proper voltage.
the chart on page 3. If Coil is open (burned out), verify that
transformer for Electric Strike has correct voltage current AC/DC
and is wired correctly. AC Coils do not operate at continuous
duty, or on DC voltage.
Check that Slider (2) floats freely, as follows:
Remove Electric Strike from jamb and hold with wires facing up.
Test that Strike is locked by applying pressure to Latch. Then
turn Strike upside down with wires facing down and verify that
Latch opens freely by applying pressure. The locking Slider (#2)
must
float freely for unit to operate properly.
Electric Strike ener-
1.
Lockset is applying pressure
Check for proper cutout installation of Electric Strike. Latch
gizes but does not
to Electric Strike, preventing
requires proper clearance to open correctly and provide path
disengage lockset
Latch from releasing.
for Lockset Latch to engage Strike.
Check that Lockset Latch is not binding to bottom of Strike cavity
due to door sag.
Check if foam insulation or the materials around door jamb are
preventing door from closing flush, causing door to put pressure
on Latch.
Possible Trouble
Probable Cause
Suggested Remedy
TROUBLESHOOTING
Содержание 4100 Electric Strike