LEFT HAND
(LH)
LEFT HAND
REVERSE BEVEL
(LRB)
RIGHT HAND
(RH)
RIGHT HAND
REVERSE BEVEL
(RRB)
OUTSIDE
OUTSIDE
DOOR HANDING GUIDE
HANDING OF DOOR IS ALWAYS DETERMINED
FROM THE OUTSIDE.
VOLTAGE DROP GUIDE
Length to Transformer
12V
24V
Up to 50 feet
18 AWG
20 AWG
50 to 150 feet
16 AWG
18 AWG
150 to 300 feet
14 AWG
16 AWG
300 to 600 feet
12 AWG
14 AWG
The TRINE MODEL # 3234, #3234W and #3478:
FAIL-SECURE
"INTERMITTENT DUTY" units are designed for
momentary application of voltage for access control purposes,
and cannot be continuously powered without permanent and
irreversible damage to the electric strike's solenoid.
The TRINE MODEL #3234-RS, #3234W-RS and #3478-RS:
FAIL-SAFE
"CONTINUOUS DUTY" versions may be used for
applications where the release must remain UNLOCKED for
extended periods. Please contact TRINE for other additional
TRINE electric release solutions for those applications requiring
a continuous duty FAIL-SECURE electric release that may be
powered for extended periods, commonly referred to as
CONTINUOUS DUTY.
The TRINE
LC version
of MODEL # 3234, 3234W, #3478, #
3234-RS, #3234W-RS and #3478-RS can be used for
"INTERMITTENT DUTY" AND "CONTINUOUS DUTY"
3000 SERIES ELECTRICAL CHARACTERISTICS CHART:
STANDARD MODELS
VOLTAGE CURRENT (AMPS)
COIL
RESISTANCE
(OHMS)
DUTY AUDIBLE
SOUND
WIRE
COLOR MODEL
12V DC
0.480
25
Int
Silent
Blue-Blue
STD
24V DC
0.240
100
Int
Silent
White-White
STD
LC & RS MODELS
VOLTAGE
CURRENT (AMPS)
PULL-IN/HOLDING
COIL
RESISTANCE
(OHMS)
DUTY AUDIBLE
SOUND
WIRE
COLOR MODEL
12V DC
0.743/0.298
13
Int./Cont.
Silent
Red-Red
LC
12V AC
0.715/0.277
13
Int./Cont.
Silent
Red-Red
LC
24V DC
0.397/0.170
13
Int./Cont.
Silent
Red-Red
LC
24V AC
0.378/0.173 13
Int./Cont.
Silent Red-Red
LC
Page 2
LUBRICATION:
The TRINE Model #3234, #3234W & #3478
do not require lubrication
. Lubricating these units will actually
hamper their performance by attracting dust and debris into the
tight tolerance precision Micro Solenoid assembly.
GETTING STARTED:
Before proceeding with your
installation, verify that the door to which the electric release is
being applied is in good working condition.
These items are essential for either new installations or retrofits
Items which should be specifically checked prior to beginning
the installation include:
The hinges (or pivots) are in good condition
If your installation is a retrofit, that the existing latch
lines up perfectly with the existing strike plate.
The door is not rubbing on the saddle or anywhere on
the frame
The door closer is not leaking and is in good condition
and properly adjusted.
The door is not warped or otherwise damaged which
might hamper its operation or otherwise affect your
installation or the final system's performance.
That the door frame member into which the door
release is to be installed is deep enough (1 inch) for the
body of the electric strike, and that the wiring to
operate the electric release can be installed for your
application.
HANDING:
The TRINE Model #3234, #3234W and #3478 are
non-handed
.
DUTY & VOLTAGES:
The TRINE Model #3234, #3234W &
Model #3478 are available as FAIL-SECURE (Normally Locked,
Power to Unlock), INTERMITTENT DUTY and are supplied in
two different operating voltage and the
LC VERSION
, suitable
for use in a range of voltages from 12V to 24V AC or DC. The
TRINE Model #3234RS, 3234WRS & Model #3478RS are FAIL-
SAFE (Normally Unlocked, Power to Lock), continuous duty and
are supplied with LC module.
LC units will operate on any input voltage from 12V to 24V AC
or DC, and offer both the benefits of reducing inventory by
enabling you to stock one strike.
In addition, they offer both
surge suppression and inductive kickback protection.
Please refer to the accompanying VOLTAGE DROP CHART for
recommended wire gauges for various voltages and wire
lengths.