Take Latch Pivot Shaft with crown end in upright position and
insert through shaft hole at the top of the frame “in” selected
handing. This will push the Assembly Pin through bottom
hole.
Place Coil at top of frame, aligning the Coil Bracket threaded
hole with the hole in the frame. The Slider tip should rest
between the side of Coil and Coil Bracket. Secure Coil to the
frame with Coil Assembly Screw (#6).
Check Slider action . Make sure Slider is free to move up and
down with no resistance.
Before replacing cover, make sure the unit operates properly
by testing with appropriate voltage.
NOTE: Do not attempt to lubricate Electric Strike!!!
Place Strike face down and place wire leads through hole in
cover. Attach cover with two screws (4).
INSTALLATION PROCEDURE:
- For new or replacement
installation in wood or metal jambs.
1. Verify that voltage rating of Electric Strike is compatible
with supply voltages of installation. Coil voltages are color
coded.
WIRE LEAD
CODE/STRIPE
12AC
Blue/Orange Stripe
12DC
2 Orange Stripe
24AC
Blue/Black Stripe
24DC
2 Black Stripe
2. Using template supplied with Electric Strike, mark door
jamb for cutout and screw holes.
NOTE
For proper installation, center line of latchset must be aligned
with center line of Electric Strike.
3. Prepare door frame (cut out jamb if required) for Electric
Strike. Leave sufficient space for splicing between power sup-
ply wiring and Electric Strike wiring.
Insert
Latch
Pin
Screw (6)
Slider must rest
inside of Coil
Assembly
Bracket
ELECTRICAL CHARACTERISTIC CHART
FAIL SECURE
(Intermittent Duty) NORMALLY LOCKED
VOLTAGE CURRENT/AMPS OHMS SOUND DUTY
12VAC
.70
4.5
Buzz
Intermittent
24VAC
.37
18.0
Buzz
Intermittent
12VDC
.28
43.0
Silent
Inter/Cont
24VDC
.15
164.0
Silent
Inter/Cont
4. If required, run new wiring to door frame mounting hole.
See figure 10 for typical wiring installations. Refer to wiring
chart below for correct wire size. (Total wiring length
includes routing to door-release push button).
Total Wiring Length
to Transformer
12V
24V
Up to 50 Ft
18AWG
20AWG
50 to 150 ft
16AWG
18AWG
150 to 300 ft
14AWG
16AWG
300 to 600 ft
12AWG
14AWG
NOTE
For DC operation, to obtain an audible signal when Electric
Strike is energized, install buzzer type BZ-12 for 12VDC
operation, or BZ-24 for 24VDC operation (purchased
seperately), as illustrated in figure 10.
5. Hold Electric Strike upright (wiring toward top) and
determine if handing is required. If so, perform handing
procedure.
6. Splice Electric Strike wiring to supply wiring. Secure
with wire nuts (supplied).
7. For wood and aluminum door jambs, drill pilot holes for
securing Electric Strike to door jamb. For steel and
aluminum door jambs, secure Electric Stike to existing
mounting tabs.
8. Install Electric Strike into door jamb and secure with flat
head mounting screws (supplied).
9. Verify that door operates correctly when Electric Strike is
energized and not energized.
110-120 VAC House Current
Primary Side (Input)
Transformer (Stepdown)
BZ 12 or BZ24
Buzzer (Optional)
Secondary Side (Output)
See Notes
Rectifier
Rectifier
Figure 10.
Figure 8.
Figure 9.
NOTES:
1. Rectifier can be located either between transformer and
push button, or between push button and electric strike.
2. Use either a silicon rectifier or a current-regulating
rectifier for converting the AC voltage at the transformer
secondary to the DC for operating the electric strike.
+
-