Trine 4100 Electric Strike Скачать руководство пользователя страница 3

TRINE 4200 

THE ONE BOX SOLUTION

FOR CYLINDRICAL LOCKS

AND DEADLATCHES

Congratulations on the purchase of this quality TRINE security 

product. This product has been designed to install easily, 

perform reliably, and provide years of trouble free security.

BEFORE proceeding with your installation, please review the 

following list of features. If you have any questions after reading this 

document please call TRINE's TECHNICAL SUPPORT 

(718) 829-2332 

EXT. 447

, or visit the TRINE web site at 

www.trineonline.com 

1440 Ferris Place   l   Bronx   l   New York  l   10461

4200

ELECTRIC

STRIKE

INSTALLATION INSTRUCTIONS

TROUBLESHOOTING THE COMPLETED INSTALLATION: 

WIRING DIAGRAMS

DO NOT APPLY A VOLTAGE OF MORE THAN 10% OVER THE 

RATED OPERATING VOLTAGE OF THE STRIKE OR THE 

SOLENOID WILL BE DAMAGED

SYMPTOM:  Electric release is not actuating:

1. Verify proper voltage is present AT THE STRIKE. If voltage is 

present, the strike may have been affected during the 

installation, or dirt or debris may be preventing proper 

operation. Ensure that all moving parts are clean. DO NOT 

LUBRICATE THE SOLENOID. 

 

2. If voltage IS NOT present: 

· Verify Circuit breaker is on

· Verify voltage at the transformer/power supply output. 

· Verify that there are no additional, external switches or  

  devices which may be interrupting your circuit.

· Check for damaged wiring or bad wire splices.

SYMPTOM:  Door will not open but strike is working

·  First, check to see if the electric strike works properly 

while the door is open.

·  Check for proper lock-latch engagement

· Check for pressure from the door on the electric strike 

by following these steps:

Push the door from the outside, try and relieve the bolt 

to latch pressure and actuate the 4200. While the 

4200 is unlatched swing the door open. If the door 

opens, then the bolt maybe applying pressure to the 

latch. Adjust the position of the 4200 to relieve the 

pressure.
Possible remedies include:

    1. Re-adjust door closer.

    2. Remove door silencers.

    3. Remove, or trim, weather stripping around the door.

    4. Adjust electric strike position if possible.

    5. Correct excessive warping of door.

PHONE: (718) 829-2332

FAX: (718) 829-6405

1440 FERRIS PLACE

BRONX, NY 10461

email: [email protected]

website: www.trineonline.com

4

 

 

    Current 

      Power

Voltage                     Draw             Consumption  Resistance

  12DC   

    .240 Amps        2.90 Watts       50 Ohms

  24DC   

    .114 Amps        2.74 Watts     210 Ohms

  12AC

 @ 50-60Hz

   .210 Amps     2.50 Watts       50 Ohms

  16AC

 @ 50-60Hz

   .281 Amps     4.48 Watts       50 Ohms

  24AC

 @ 50-60Hz

   .420 Amps      10.08 Watts       50 Ohms

4200 ELECTRICAL CHARACTERISTICS:

Mount the shim with the step aligned

with the top of the latch as so.

This position will ensure that the cylindrical

lock's auxilliary trigger will function properly.

USING THE LATCH SPACER SHIM

The latch spacer shim is used to make an adjustment to 

minimize the space between the door's inside face and the door 

stop, or reduce door play. For cylindrical locks aligning to the 

vertical center of the strike mount the shim as shown below.

OPERATING TEMP RANGE:  -

20°C TO +40°C

DO NOT APPLY A VOLTAGE OF MORE THAN 10% OVER THE RATED

OPERATING VOLTAGE OF THE STRIKE OR THE SOLENOID WILL BE DAMAGED

When removing the connector and using the wires direct;  Blue Wire is Common,

Red Wire accepts 12DC & 12-16AC, Brown Wire accepts 24DC.

RS IS FAILSAFE ACTION (LOCKS WITH POWER) AND IS DC ONLY

24V DC OR 12V DC

TRANSFORMER

TO 120V AC LINE

PUSH

BUTTON

NORMALLY

CLOSED

+

-

FAIL-SAFE

ELECTRIC STRIKE

USE THE PROPER

CONNECTOR 12VDC OR 24VDC

ASSEMBLY FOR 

THE 4200 STRIKE

Cannot use AC in Fail Safe Configuration

24V DC OR 12V DC TRANSFORMER

TO 120V AC LINE

PUSH

BUTTON

NORMALLY OPEN

+

-

USE THE PROPER

CONNECTOR 12VDC OR 24VDC

ASSEMBLY FOR 

THE 4200 STRIKE

For AC use the 12 VDC connectors

For 12 - 24 VAC use 50-60 Hz

FAIL-SECURE

ELECTRIC STRIKE

V. 14.0218

CL

 3 3/8" 

 4 7/8" 

 4 1/8" 

 1 1/4" 

 1/4" 

 1 3/4" 

BACKSET

1 1/16"

 1 5/8" 

1/2”

CAVITY DEPTH

 25/32" 

32D 

(630) Satin Stainless

ALUM

 Aluminum Powder Coat

BLK 

Black Powder Coat

DKBZ

 Dark Bronze Powder Coat

GRN

 Green Powder Coat

WHT

 White Powder Coat

AVAILABLE FINISHES

1 - (1) 4200 Electric Strike Mechanism

2 - (4) Faceplates as shown

3 - (6) #12-24 x 1/2 inch Philips Mounting Screws 

4 - (2) #12-24 Lock Nut

5 - (2) Quick Connect Socket & Wire Assembly 12VDC & 24VDC Version

6 - (2) Sealed Crimp Connectors

7 - (1) Latch Spacer Shims & (2) Mounting Screws

8 - (1) Frame Trim Skirt & (2) Screws 

9 - (2) Mounting Tabs

WHAT'S IN THE BOX:

Auxilliary Trigger

PREMIUM TRIM SKIRT FOR THE 4200

USING THE TRIM SKIRT

The skirt can be used to clean up the 

cut line of the frame face during 

installation.  The Trim Skirt comes 

with 2 longer screws (included) for 

fastening to the top and bottom of 

the 4200.

Available in 5 powdercoat finishes: 

Aluminum (ALUM),  Black (BLK), Dark 

Bronze (DKBZ), Green (GRN), and 

White (WHT) which can match the 

finish of the faceplate and Fascia’s.

RS IS FAILSAFE ACTION (LOCKS WITH POWER) AND IS DC ONLY

Содержание 4100 Electric Strike

Страница 1: ...rike position if possible 5 Correct excessive warping of door USING THE LATCH SPACER SHIMS CONTINUED For locks not aligning to the vertical center of the strike mount the shims as shown below Most if...

Страница 2: ...nnect socket to the power wires coming out of the frame 5 Connect the strikes bottom terminal to the quick connect socket 6 Tuck the wires inside the door frame 7 Install the electric strike into the...

Страница 3: ...s 50 Ohms 24AC 50 60Hz 420 Amps 10 08 Watts 50 Ohms 4200 ELECTRICAL CHARACTERISTICS OPERATING TEMP RANGE 20 C TO 40 C DO NOT APPLY A VOLTAGE OF MORE THAN 10 OVER THE RATED OPERATING VOLTAGE OF THE STR...

Страница 4: ...ON FACEPLATE DIMENSIONS Metal Frame TAB DIMENSIONS Wood Frame Use 12 24 x 1 2 inch Philips Mounting Screws for tab holes Aluminum Frame MOUNTING TABS 2 SUPPLIED 4 7 8 1 17 64 4 1 8 3 3 8 1 1 16 8 1 16...

Страница 5: ...power ONLY as the last step 3 Carefully choose the quick connect socket to match the required voltage The quick connect sockets are labeled 12VDC Blue Wire or 24VDC White Wire 4 Use the crimp connecto...

Страница 6: ...or 4 Adjust electric strike position if possible 5 Correct excessive warping of door PHONE 718 829 2332 FAX 718 829 6405 1440 FERRIS PLACE BRONX NY 10461 email customerservice trineonline com website...

Страница 7: ...WITCH NORMALLY CLOSED FAIL SAFE CONFIGURED STRIKE USE 12V THRU 24V AC OR DC TRANSFORMER TO 120V AC LINE WIRING FOR FAIL SAFE MODE WITH OPTIONAL BUZZER SWITCH SINGLE POLE DOUBLE THROW FAIL SAFE CONFIGU...

Страница 8: ...WITCH NORMALLY CLOSED FAIL SAFE CONFIGURED STRIKE USE 12V THRU 24V AC OR DC TRANSFORMER TO 120V AC LINE WIRING FOR FAIL SAFE MODE WITH OPTIONAL BUZZER SWITCH SINGLE POLE DOUBLE THROW FAIL SAFE CONFIGU...

Страница 9: ...le the 4850 is unlatched swing the door open If the door opens then the bolt maybe applying pressure to the latch Adjust the position of the 4850 to relieve the pressure POSSIBLE REMEDIES 1 Re adjust...

Страница 10: ...Push the anchor pins in the back of any 4850 series strike if you desire to use this Figure 5 Crimp the quick connect socket assembly to the power wires Crimp Connectors Quick Connect Socket Assembly...

Страница 11: ...tch cavity Having the latch on center will ensure that the sensor will have enough surface to detect You can use the 1 8 and 1 4 spacer included 1 4 is for 4850LB only to move the 4850LB 4800FLB close...

Страница 12: ...RELAY PANEL INDICATOR OR OTHER SIGNALING DEVICE POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 3 CONTROL PANEL PANEL SIDE WIRING FRAME SIDE WIRING Hook up to either Normally Open or Normally Closed Termin...

Страница 13: ...Solid Cast Latch Stainless Steel Cavity Width 5 8 Height 1 1 8 Depth 1 2 Non handed Heavy duty latch spring Silent Operation Intermittent Duty with the Standard versions Intermittent and Continuous D...

Страница 14: ...ubricating these units will actually hamper their performance by attracting dust and debris into the tight tolerance precision Micro Solenoid assembly GETTING STARTED Before proceeding with your insta...

Страница 15: ...ed to as Silent Operating unlike some types of AC electric releases which make a buzzing sound when activated For some applications such as entrances into apartment buildings or storerooms an audible...

Страница 16: ...16 1 1 32 1 1 4 3 1 8 1 1 8 1 5 16 9 16 3 32 5 16 1 OPTIONAL 1 16 THICK SHIM Page 4 4 7 8 1 1 4 1 7 8 1 1 32 1 11 16 1 3 32 4 1 8 3 4 3 11 32 5 8 3 8 OPTIONAL 1 16 THICK SHIM 1 1 4 4 7 8 3 32 1 1 16...

Страница 17: ...he 3234 s 2 3 4 x 1 1 4 faceplate requires the least amount of jamb preparation when compared with other electric strikes WIRING DIAGRAM 24V DC OR 12V DC TRANSFORMER OPTIONAL BUZZER BZ 12 or BZ 24 TO...

Страница 18: ...serviceable part Note that intermittent coils can only receive power for 1 minute or less 3 If voltage IS NOT present Verify Circuit breaker is on Verify voltage at the transformer power supply output...

Страница 19: ...power to the receptacle into which you will plug your transformer power supply This will enable you to safely cut power during installation and permit troubleshooting if required 5 Verify that the rec...

Страница 20: ...must remain UNLOCKED for extended periods or when required by code The TRINE LC version of MODEL 3258 3458 3258RS and 3458RS can be used for INTERMITTENT DUTY AND CONTINUOUS DUTY ELECTRICAL If you ar...

Страница 21: ...a buzzing sound is distracting or disturbing Verify with your client which they require and if an audible signal when the electric release is activated is desirable then add a audible visual annunciat...

Страница 22: ...AC TRANSFORMER PUSH BUTTON NORMALLY OPEN The rectifier can be positioned before of after the push button in the circuit The LC module can ONLY be positioned after the push button as shown above The L...

Страница 23: ...8 2 7 16 5 8 13 16 2 1 8 1 11 16 1 1 32 1 11 16 1 1 8 ALUMINUM FRAME INSTALLATION The 3458 s 4 5 8 x 1 9 16 full lip steel faceplate requires the least amount of jamb preparation when compared with ot...

Страница 24: ...maged wiring or bad wire splices SYMPTOM Door will not open but strike is working Check for other locks on door Check for proper lock latch engagement SEE SECTION CONFIRMING PROPER LOCK LATCH ENGAGEME...

Страница 25: ......

Страница 26: ...s 2 12 24 x 1 2 EN MTS 14 Shim Kit 3 1 16 Shim EN UNV SHIM 15 Shim Screws 2 6 32 x 1 4 EN SHIM SCR S 16 Shim Screws 2 6 32 x 3 8 EN SHIM SCR L Figure 1 EN400 Electric Strike NOTE Number in parenthesis...

Страница 27: ...all the pivot holes lines up Assemble the Solenoid and secure it with the solenoid Screw as shown Finish the assembly by installing the Cover and securing it with the two assembly Screws Assemble the...

Страница 28: ...the or BLACK negative side wire terminal to the negative side of the circuit RED BLACK INSTALLATION PROCEDURE For new or replacement installation in wood or metal jambs 1 Verify that voltage rating of...

Страница 29: ...releases and that there is sufficient Spring tension to push it to closed positionwhen released If Latch does not have Spring tension disassemble Electric Strike and inspect for improperly installed...

Страница 30: ...icates part in Parts List UL LISTED 10B fire rated class A 3 hour Single Swing Doors UL LISTED 1034 Burglary Resistant Locking Mechanism for Indoor or Outdoor Use ANSI BHMA A156 5 1992 4 7 8 X 1 1 4 F...

Страница 31: ...e to fail safe when replaced with special order part EN SLR RS When using the fail safe Slider a DC Coil must be used The fail safe Slider is identified by the small dimple below the welded tip CHANGI...

Страница 32: ...be employed ELECTRICAL CHARACTERISTICS CHART FAIL SECURE Intermittent Duty NORMALLY LOCKED VOLTAGE CURRENT AMPS OHMS SOUND DUTY 12 VAC 70 4 5 Buzz Intm 24 VAC 37 18 0 Buzz Intm 12 VDC 28 43 0 Silent...

Страница 33: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 34: ...Figure 1 EN800 Electric Strike NOT PART OF ASSEMBLY USED ONLY DURING DISASSEMBLY OR CHANGING FAIL SECURE ACTION UNLESS OTHERWISE SPECIFIED FRAME IS SUPPLIED AS SATIN STAINLESS STEEL US32D SPECIFY OTHE...

Страница 35: ...The EN Electric Strike must be installed with coil assembly up wiring toward top of unit In this position the Electric Strike will be locked without power Fail Secure or locked with power Fail Safe ac...

Страница 36: ...AGE CURRENT AMPS OHMS SOUND DUTY 12VAC 70 4 5 Buzz Intermittent 24VAC 37 18 0 Buzz Intermittent 12VDC 28 43 0 Silent Inter Cont 24VDC 15 164 0 Silent Inter Cont 4 If required run new wiring to door fr...

Страница 37: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 38: ...7 Frame EN 9 FR 8 Assembly Pin EN ASS PN 9 Spring EN SPR 10 Latch Pivot Shaft EN LCH PV ST 11 Guard EN GRD 12 Plastic Cap EN PLC 13 Support Plate EN 9 SP 14 Mounting Screws 2 12 24 1 2 EN MTS 15 Shim...

Страница 39: ...E The EN Electric Strike must be installed with coil assembly up wiring toward top of unit In this position the Electric Strike will be locked without power Fail Secure or locked with power Fail Safe...

Страница 40: ...AGE CURRENT AMPS OHMS SOUND DUTY 12VAC 70 4 5 Buzz Intermittent 24VAC 37 18 0 Buzz Intermittent 12VDC 28 43 0 Silent Inter Cont 24VDC 15 164 0 Silent Inter Cont 4 If required run new wiring to door fr...

Страница 41: ...ric Strike or Coil Assembly Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted If voltage is too low because wire size is too small for length or w...

Страница 42: ...t go into slots Fail Safe Indication Back Case 2 Insert assembly pin provided to remove latch pin latch Note The slider should fall thru the strike body after latch is removed remove slider slider gua...

Страница 43: ...r as shown Replace back cover Replace 2 screws and tighten 9 Replacing coil assembly Note Slider must be in position between brackets of coil assembly Note Position wires thru slot toward front of the...

Страница 44: ...n provided to remove latch pin latch Note The slider should fall thru the strike body after latch is removed remove slider slider guard 3 To change the action remove the slider from the frame and reve...

Страница 45: ...e sure slider is free to move up down with no resistance 12 Thread wires thru cover as shown Replace back cover Replace two 1 8 screws and tighten 10 Replacing coil assembly Note Slider must be in pos...

Страница 46: ...k up to either Normally Open or Normally Closed Terminal EN400 EN800 EN850 EN950 EN960 LBSM WIRING SCHEMATIC SWITCHED POWER CONSTANT POWER FIVE WIRE SCHEMATIC UTILIZING ONE TRANSFORMER This wiring arr...

Страница 47: ...DULE CONSTANT POWER 1440 Ferris Place Bronx New York 10461 SIX WIRE SCHEMATIC UTILIZING TWO TRANSFORMERS This wiring arrangement is used to isolate the strike operation from the LB and or the SLIDER s...

Страница 48: ...about approved installation procedures Contact rating 10 Amps at 120 volts 5 Amps at 250 volts DO NOT EXCEED CONTACT RATING CONTENTS 1 UL CSA listed switch 1 Faceplate 2 Wire leads UL Listed w Connect...

Страница 49: ...if used Insulate all connections with wire nuts or tape approved by local codes The door switch can be mounted to the switch case with the 2 flat head screws supplied In the event that the light stays...

Страница 50: ...ing 5 Battery compartment BATTERY INSTALLATION This unit operates on 3VDC batteries using 2 pieces UM 2 size C 1 5V R14 batteries or equivalent Press and slide out the battery door insert batteries in...

Страница 51: ...t 2b Fix Move away from concrete 3a Possible Cause Chime Transmitter are installed too far apart over 100 feet 3b Fix relocate pieces closer to one another C Problem Chime sounds when not intended 1 P...

Страница 52: ...t 2b Fix Move away from concrete 3a Possible Cause Chime Transmitter are installed too far apart over 100 feet 3b Fix relocate pieces closer to one another C Problem Chime sounds when not intended 1 P...

Страница 53: ...ompartment polarity may damagethe unit FEATURES 1 Easy installation 2 Audible alarm for doors windows 3 105dB instant alarm 4 LR44 battery 3 pcs Check that the batteries are installed with correct pol...

Страница 54: ...n the battery becomes weak then it s time to replace the batteries If the unit functions abnormally first check the battery and replace as required The unit is composed of two parts the audible transm...

Страница 55: ...61 3699 PH 718 829 2332 FAX 718 829 6405 E mail customerservice trineonline com www trineonline com 230 8 Note 231 2 Note Push Button Instructions Expand Your Wireless Chime System The 2 note 231 8 no...

Страница 56: ...sh button and chime codes are the same Check orientation of push button battery Check charge of push button and chime batteries replace if necessary Batteries seem OK but the chime doesn t work when i...

Страница 57: ...might require the use of tweezers to remove and replace the jumpers ONE YEAR LIMITED WARRANTY TRINE ACCESS TECHNOLOGY reserves the right to discontin ue and to change specifications at any time witho...

Страница 58: ...s Dong one note and Ding Dong two note The factory setting is for the Ding Dong tune This tune can be changed by following the instructions below Dong one note tune Push button Add jumper to location...

Страница 59: ...s to mount base to wall 5 Connect wires to terminal screws marked Front Transformer and Rear on the chime base 6 Place chime cover securely over the base NOTE FOR LOUDER SOUNDING CHIME PERFORMANCE A 2...

Страница 60: ...w radiant receiver SPECIFICATIONS 1 BOTH PUSH BUTTONS ON THE 018 2 WILL TRIGGER THE 017TDC 2 The 017TDC 2 3 will work with a range of operating voltages These voltages are from 12 Volts through 30 Vol...

Страница 61: ...ITCHES FIGURE 4 TRANSFORMER For DC ONLY For DC ONLY For DC ONLY For DC ONLY Power Supply 12 30 V AC DC Fail Secure Strike 1 Fail Secure Strike 2 USE THE COPPER SHUNT INCLUDED TO SUPPLY POWER TO THE ST...

Страница 62: ...e receiver and the 018 2 transmitter SECURITY CODE SWITCHES FIGURE 8 EXAMPLE CODE SETTING MUST BE THE SAME SWITCH COMBINATION FIGURE 9 FIGURE 10 TIME DELAY KNOBS 017TDC 2 017TDC 3 3 Optionally you can...

Страница 63: ...ections may be faulty Security Code mismatch Wiring connection may be faulty RF interference Security Code mismatch Faulty power supply Loose wiring connections or shorted wire Replace the battery Use...

Страница 64: ...sen the transmitter s assembly screw and snap the front cover open Match the coding of the receiver Figure 1 below shows the location of the DIP switches for the 017TDC 2 3 receiver and the 018 2 tran...

Страница 65: ...hances of installation success Before screwing the 017TDC receiver down choose an initial location and use a 10 feet electrical cord and walk test the 017TDC s sensitivity to receive the 018 2 s signa...

Отзывы: