VAV VV550 Controller Programming and Operation
commissioning test sequence starts. The fields are updated with the results as the sequence
progresses. The data is held until the next auto-commissioning test.
If an auto-commission command is received in the middle of an auto-commissioning cycle the
auto-commissioning sequence restarts. If an auto-commission command is received during
calibration, calibration aborts and restarts after auto-commissioning finishes. If an abort auto-
commission command is received during the calibration portion of the primary air valve test, it is
honored after the air valve calibration finishes.
The mode field of reported unit status reports TEST when the controller is in the auto-
commissioning sequence.
Table 9.
Auto-commissioning test sequence
Item
Test Action
Reported Data
Primary air valve
and airflow
(a)
1. Turn off fan and reheat.
2. Close air valve and modulating water valve (if present).
3. Calibrate the airflow sensor.
4. Open the air valve to 40% of the configured maximum airflow. Record the position of the air valve.
5. Open the air valve to 100% of the configured maximum airflow. Record the position of the air valve.
Primary air valve
position at 40% and
100% flow.
Fan Flow
(b)
1. Record the auxiliary temperature at the configured maximum airflow.
2. Close the primary air valve.
3. Turn on the fan (if present).
4. Monitor auxiliary temperature for 3 minutes or until it changes by 10°F.
5. Record the auxiliary temperature.
Starting and ending
auxiliary
temperature.
Local Reheat
Hydronic
(b)
1. If no fan is present, open the air valve to the configured minimum local heating airflow.
2. If the fan is present, close the air valve and turn on the fan.
3. Record the auxiliary temperature.
4. Open the water valve to 100% open.
5. Monitor the auxiliary temperature for 10 minutes or until it changes by 10°F.
Starting and ending
auxiliary
temperature.
Local reheat
electric
(b)
1. If no fan is present, open the air valve to the configured minimum local heating airflow.
2. If the fan is present, close the air valve and turn on the fan.
3. Record the auxiliary temperature.
4. Progressively turn on each local stage 30 seconds after the previous stage until all stages are
energized.
5. Record the auxiliary temperature 30 seconds after each stage is energized.
Starting auxiliary
temperature and
the auxiliary
temperature for
each local stage of
electric heat
energized.
(a) If there is no flow sensor, the controller runs in pressure dependent mode and record 40% and 100% during this auto-commissioning step.
(b) Requires a functional auxiliary sensor in the discharge air stream. The auxiliary sensor must be configured for discharge air temperature.
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......