VAV VV550 Controller Device Home Tabs: Instructions
Chapter Overview
This chapter contains information about the following:
•
Setpoints Tab
•
Unit Tab
•
Setup Tab
•
Inputs Tab
•
Outputs Tab
•
Test Tab
•
Other Tab
Configuration
To access the data fields for each tab and to make adjustments, select the
Configure
button. To
make adjustments, find the correct parameter, change it, and download to VV550.
Setpoints Tab
In Rover, the setpoints can be changed by selecting the
Configure
button. Following are
descriptions of each line on the
Setpoints
tab.
Default Setpoints
Unoccupied Cooling:
Set points have a range of 30.0° - 100.0°F (-1.1° - 37.8°C). This cooling set
point is used when the VAV VV550 Controller is unoccupied. The unoccupied cooling set point must
be greater than or equal to the unoccupied heating set point plus 2.0°F 1.1°C).
Figure 42. Setpoints tab
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......