46
VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation
Pressure independent control - When a valid flow value is present, the controller operates under
pressure independent control. If after an airflow sensor failure, the airflow returns to the valid range
(airflow value greater than 10% of configured nominal airflow), the controller automatically
resumes pressure independent control.
Initiate Calibration button:
The calibration sequence enables the controller to calibrate the air
valve position and the water valve position.
Unit Description
Describes the type of device being communicated to via Rover service tool. It also indicates the
general program that has been placed in controller.
Outputs Tab
Fan Status:
The Fan will be shown as On, Off, or None.
Air Valve Position:
Indicates air valve or damper position.
Reheat Capacity:
Will indicate reheat capacity in Percentage.
Figure 34. Outputs tab
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......