Unit Tab
In Rover, the Unit Tab can be changed by selecting the
Configure
button. Following are
descriptions of each line on the Unit tab.
Unit Configuration
This allows for selection between three operational programs. The three programs are Space
Temperature, Ventilation Flow, and Flow Tracking
Note:
See Operation chapter fore details on operational programs.
Default Primary Air Temperature
The selections are cooling or heating. The controller default operation (auto) can place the unit in
heating or cooling mode. When the controller automatically determines the heating or cooling
mode, the unit switches to the desired mode based on the primary air temperature.
Note:
It can also be done with a communicated request.
Primary Air Setup
Auto Changeover Setpoint:
The auto change over set point allows for switching from heating
to cooling operation with the vav) If primary air temperature greater than the configured auto
changeover setpoint, then primary air temperature is. (Primary air is hot enough for heating and
reheat can be used.) If primary air temperature < configured auto changeover setpoint - 10°F
(5.56°C), then primary air temperature is cold. (Primary air is cold enough for cooling and reheat
can be used.) No change in hysteresis region.
Reheat Setup
Reheat Enable Setpoint:
When the primary air temperature is greater than the configured reheat
enable setpoint, reheat is turned OFF until the primary air temperature drops 5°F (2.78°C) below
Figure 43. Unit tab
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......