VAV-SVP01A-EN
VAV Start Up/Check Out Procedure
Wiring requirements
The recommended Comm5 communication-link wiring is 22 AWG, Level 4, twisted-pair wire. See
Table 5, p. 20
"Specifications for Level 4-compliant cables". The wire can be either shielded or
unshielded. However, unshielded wire is recommended for most installations.
The maximum wire length for Comm5 communication links is 4,500 ft (1,400 m). Comm5
communication-link wiring must be installed in a daisy-chain configuration (
Figure 4, p. 21
and
Figure 5, p. 22
).
Table 5.
Cable specifications
Specification
Value
dc resistance
(Maximum resistance of a single copper conductor regardless of whether or not it is solid or stranded and regardless
of whether or not it is metal coated.)
18.0
Ω
/1,000 ft 20°C
dc resistance unbalance (maximum)
5%
Mutual capacitance of a pair (maximum)
17 pF/foot
Pair-to-ground unbalance (maximum)
1,000 pF/foot/1,000 ft
Characteristic impedence
772 kHz
102
Ω
±
15%
1.0 MHz
100
Ω
±
15%
4.0 MHz
100
Ω
±
15%
8.0 MHz
100
Ω
±
15%
10.0 MHz
100
Ω
±
15%
16.0 MHz
100
Ω
±
15%
20.0 MHz
100
Ω
±
15%
Attenuation (maximum dB/1,000 ft at 20°C)
772 kHz
4.5 dB/1,000 ft at 20°C
1.0 MHz
5.5 dB/1,000 ft at 20°C
4.0 MHz
11.0 dB/1,000 ft at 20°C
8.0 MHz
15.0 dB/1,000 ft at 20°C
10.0 MHz
17.0 dB/1,000 ft at 20°C
Worst-pair near-end crosstalk (minimum)
(Values shown are for information only. The minimum NEXT coupling loss for any pair combination at
room temperature is to be greater than the value determined using the formula NEXT (F
MHz
)>NEXT
(0.772)-15
log10
(F
MHz
/0.72) for all frequencies in the range of 0.772 MHz-20 MHz for a length of 1,000
ft.)
772 kHz
58 dB
1.0 MHz
56 dB
4.0 MHz
47 dB
8.0 MHz
42 dB
10.0 MHz
41 dB
16.0 MHz
38 dB
20.0 MHz
36 dB
dc resistance unbalance (maximum)
5%
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......