VAV-SVP01A-EN
63
VAV VV550 Controller Device Home Tabs: Instructions
Outputs Tab
In Rover, the Outputs Tab can be changed by selecting the
Configure
button. Following are
descriptions of each line on the Outputs tab. For the factory-installed VAV VV550 Controller, all
inputs and outputs are configured at the factory. For the field-installed VAV VV551 Controller, click
the Start button to configure the outputs.
Binary Output 1
Binary output 1 is used to drive the air valve closed. It works in conjunction with binary output 2
to modulate the air valve.
Binary Output 2
Binary output 1 is used to drive the air valve open. It works in conjunction with binary output 1 to
modulate the air valve.
Output Configuration Wizard
Click the Start button to configure the outputs.
Binary Output 3& 4
This output can be configured for:
•
Hot-water on/off control
•
Hot-water modulating (3-wire) valve control (requires outputs 3 and 4)
•
Electric-heat staged or pulse width modulation
The output is automatically configured based on your answers in the Output Configuration Wizard.
Device Contacts Normally Open:
Select this check box if the device contacts are normally open.
This check box is available only for hot-water on/off control.
Figure 46. Outputs tab
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......