72
VAV-SVP01A-EN
Sequence of Operations
Space Temperature Control: Fan-Powered Units
VAV VV550/VV551 Controllers provide three fan options when in space temperature control mode:
•
One-speed ON/OFF series fan;
•
One-speed ON/OFF parallel fan;
•
Fan Off Delay
Table 11. Local heat only with no fan present
Configuration
Method of control
Local
Remote
Stage 1
Stage 2
Stage 3
PWM electric
(1 to 3 stages)
Not applicable Local PI capacity loop
Each stage represents an equal percentage of total capacity PWM Output (one stage = 100%; two stages
= 50% each; three stages = 33.33% each). Total capacity is limited by communicated auxiliary heat enable.
On/Off electric
(1 to 3 stages)
Not applicable Local thermostatic
On: Zt < HSP
Off: Zt
≥
HSP + 0.5°F (0.28°C)
Local thermostatic
On: Zt < HSP - 1°F (0.56°C)
Off: Zt
≥
HSP - 0.5°F (0.28°C)
Local thermostatic
On: Zt < HSP - 2°F
Off: Zt
≥
HSP - 1.5°F
Each stage represents an equal percentage of total capacity. Total capacity is limited by communicated
auxiliary heat enable.
On/Off hot water
(1 stage)
Not applicable Local thermostatic
On: Zt < HSP
Off: Zt
≥
HSP + 0.5°F (0.28°C)
Not applicable
Not applicable
Total capacity is limited by
communicated auxiliary heat
enable.
Not applicable
Not applicable
Modulating hot
water
Not applicable Local PI capacity loop
Modulating valve capacity = Total capacity
Valve drive Incrementally open/closed
Total capacity limited by communicated auxiliary heat enable
Not applicable
Note:
Abbreviations: Zt = Zone temperature; HSP = Heating setpoint
Table 12. Local heat only with parallel/series fans present
Configuration
Method of control
Local
Remote
Stage 1
Stage 2
Stage 3
Fan
Not applicable
Parallel/Series Fans
Not applicable
Not applicable
Fan +
PWM electric
(1 to 2 stages)
Not applicable
Parallel/Series Fans
Local PI capacity loop
Each stage represents an equal percent of total capacity (1-stage = 100%, 2
stages = 50% each) PWM output
Total capacity is limited by communicated auxiliary heat enable.
Fan +
On/Off electric
(1 to 2 stages)
Not applicable
Parallel/Series Fans
Local thermostatic
On: Zt < HSP - 1°F (0.56°C)
Off: Zt
≥
HSP - 0.5°F (0.28°C)
Local thermostatic
On: Zt < HSP - 2°F (1.11°C)
Off: Zt
≥
HSP - 1.5°F (0.83°C)
Each stage represents an equal percentage of total capacity. Total capacity is
limited by communicated auxiliary heat enable.
Fan +
On/Off hot water
(1 to 2 stages)
Not applicable
Parallel/Series Fans
Local thermostatic
On: Zt < HSP - 1°F (0.56°C)
Off: Zt
≥
HSP - 0.5°F (0.28°C)
Not applicable
Total capacity is limited by
communicated auxiliary heat enable
Not applicable
Fan +
Modulating hot
water
Not applicable
Parallel/Series Fans
Local PI capacity loop
Modulating valve capacity = Total capacity
Valve drive incrementally open/closed
Total capacity limited by communicated auxiliary heat enable
Note:
Abbreviations: Zt = Zone temperature; HSP = Heating setpoint
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......