86
VAV-SVP01A-EN
Troubleshooting
Resetting Diagnostics
A reset clears latching diagnostics and enables the controller to try to run normally. If the latching
condition is still present after the reset, the controller shuts down. A reset resets a unit that is
running normally. There are five ways to reset unit diagnostics:
•
Manual output test at the controller
•
Cycling power to the controller
•
BAS (communicated status request, clear alarm)
•
Rover service tool (communicated status request, clear alarm)
•
A communicating device able to access the controller diagnostic reset input (communicated
status request, clear alarm)
LED Operation
Red Service LED
Service Push Button
Important:
If the Service button is held down for more than 15 seconds, the controller will
uninstall itself from the Comm5 network. The red service LED flashing
approximately once every two seconds indicates this mode (see Red service LED
above). Use the Rover service tool to restore the unit to normal operation. Refer the
Rover product literature for more information.
The Service push button can be used, as one of several methods, to install the controller in a
communication network. Refer to the Rover service tool product literature for more information.
Green Status LED
The green status LED is typically used to indicate whether or not the controller is powered On
(24VAC). This is the only LED under direct software control. The green status LED is Off when you
press the Test button. The green status LED blinks during manual output testing.
Table 18, p. 87
shows and describes the green status LED activity.
Table 17.
Red service LED activity
Red Service LED Activity
Description
LED is Off continuously after power is applied to the
controller.
Normal operation
LED is On continuously, even when power is first applied to
the controller.
Someone is pressing the Service push button or the
controller failed.
LED flashes approximately once every two seconds.
Uninstalled (normal controller mode). Use the Rover™
service tool to restore the unit to normal operation. Refer
to the Rover product literature for more information.
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......