92
VAV-SVP01A-EN
Troubleshooting
1.
wireless zone sensor system failure.
•
Observe LED5 on the receiver. LED5 will be On solid green whenever the receiver is
powered.
•
Make sure the receiver is properly grounded. Both the black wire (GND SIGNAL) and the
yellow wire (GND-POWER) must be grounded.
•
Press the Test button (S5) on the sensor. Models WTS, WZS LED5 should turn On solid green,
indicating proper battery strength. LED1, LED2, and LED3 will indicate signal strength (See
Table 23, p. 93
).
Table 20. Diagnostics on the sensor
LED state when Test button is pressed
(WTS, WZS sensors)
Error code (WDS
sensor display)
Indicates…
N/A
E0, E5, E7
Sensor failure
- Replace sensor
LED1: Off
LED2: Off
LED3
(a)
: 1-blink pattern repeated 3 times
E1
Disassociated
- Sensor is not associated with a receiver
LED1: Off
LED2: Off
LED3
(a)
: 2-blink pattern repeated 3 times
E2
Address set to 000
- Address not set to between 001-999
LED1: Off
LED2: Off
LED3
(a)
: 3-blink pattern repeated 3 times
E3
Software error
- Replace sensor
LED1: Off
LED2: Off
LED3
(a)
: 4-blink pattern repeated 3 times
E4
Input voltage too high
- No RF transmission is permitted with an input battery voltage
greater than 3.9V
(a) Blink pattern is On for 1/4s, Off for 1/4s, with 2s OPff between repetitions.
Table 21. Diagnostics on the receiver
LED state
Indicates…
LED1: Off
LED2: Off
LED3: 1-blink pattern repeated continuously
(a)
Disassociated
* Receiver is not associated, waiting for a sensor
* Receiver lost communication with sensor
* Receiver has no devices on its wireless personal area network
* Association with a device has been manually removed
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated continuously
(a)
Address set to 000
* Address not set to between 001-999
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated continuously
(a)
Not configured
* Receiver configuration properties bot properly set (defective
receiver)
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
Table 22. Battery status: LED5 on the sensor
User Action
LED Display
Indicates…
Press Test
Button (SS)
Solid green for 5 seconds
Battery condition is adequate for proper operation.
Solid red for 5 seconds
Battery condition is low. Batteries should be replaced.
No light
Batteries are totally dead or not installed properly, or sensor
is defective.
None
Blinking red: 1-blink pattern
1
repeated 5
times. Cycle repeats every 15 minutes.
Battery condition is low. Approximately 14 days of operation
remain before the battery is too weak to power the sensor.
Note:
1 Blink pattern is On for ¼ s, Off for 3/4 s, with 2 s Off between repetitions.
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......