VAV-SVP01A-EN
93
Troubleshooting
Note:
When checking signal strength, both LED1 and LED3 on the receiver and sensor should
illuminate in unison if the sensor and receiver are associated. Use this feature to confirm
association. If not associated, see setup procedures in Wireless chapter. If unit still does not
work proceed in checking Receiver and sensor with testing procedures below.
2. Procedure for Testing the Receiver
•
Make sure the receiver is powered.
•
Set the receiver address to 000 to force the zone temperature output and zone temperature
setpoint output to their test mode values (see
Table 24, p. 94
).
Table 23. Signal quality: LED1, LED2, LED3 on the sensor
User Action
LED Display
Indicates…
None
LED1:Off
LED2:Off
LED3:Off
Normal state
* No Test button press
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3:Off
Associated; no communication with receiver
* Associated, but no signal from the receiver after
pressing Test button
Press Test
Button (SS)
LED1:On
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Excellence signal quality
* Adequate signal margin for reliable communication.
Press Test
Button (SS)
LED1:Off
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Marginal signal quality
* Reduced battery life likely.
* Consider moving the sensor or receiver to a better
location.
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3:On
Displays for 5 seconds, then constantly off
Poor signal quality
* Unreliable communication.
* Strongly recommend moving the sensor or receiver to
a better location.
Figure 56. Receiver wiring connections
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......