VAV Start Up/Check Out Procedure
Replacing and Securing the Receiver Cover
1.
To replace the receiver cover on the base plate, hook the cover over the top of the base plate.
Apply light pressure to the bottom of the cover until it snaps in place.
2. If necessary to keep the cover securely attached, install the security screw into the bottom of
the receiver (
Figure 13, p. 32
).
Table 8.
Wiring harness: wire identification
Wire Label
Color
Function
HEATING SET
Brown
Space temperature heating setpoint
(WDS only)
FAN SYSTEM
Green
Fan and system control (WDS only)
SETPOINT
Red
Space temperature setpoint (WDS and
W2S only)
ZONE
White
Zone temperature
GND-SIGNAL
Black
Ground for setpoint and zone signal
24VAC/DC
Blue
24VAC/vdc power
GND-POWER
Yellow
Ground for 24VAC/dc
Figure 13. Snap receiver cover on base plate and attach security screw
Security screw
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......