VAV VV550 Controller Programming and Operation
VV550 Controller Device Home Tabs: At a Glance
Unit Information Tab
Space Temp:
The temperature, as reported by the zone sensor.
Active Setpoint:
The active (or actual) setpoint currently used by the VAV VV550 Controller. Can
be either Heating or Cooling depending on operating mode.
Primary Air / Discharge Air Temperature:
Shows the auxiliary temperature input.
Note:
This will be defined in configuration as either Primary Air or Discharge air temperature
depending on unit control strategies. See Configuration section for more details.
Airflow:
Measured in CFM. When a valid flow value is present, the controller operates under
pressure independent control. If after an airflow sensor failure, the airflow returns to the valid range
(airflow value greater than 10% of configured nominal airflow), the controller automatically
resumes pressure independent control. When the communicated airflow setpoint is invalid, the
flow sensor has failed, or calibration has failed, the controller closes the air valve if the configured
Figure 33. Unit tab
Содержание VAV VV550 LonTalk
Страница 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Страница 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Страница 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Страница 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Страница 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Страница 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Страница 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...
Страница 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...
Страница 115: ......