86
Monobloc Outdoor Unit Installation Manual
IMPORTANT:
It is therefore not possible to optimise the refrigerant charge in the heating mode after a leak. The unit
must be operated in the cooling mode to check, if an additional charge is required.
Saturated temperatures based on the gauge pressure (in kPa g)
Saturated
Temp. °C
Gauge pressure
(kPa g)
Saturated
Temp. °C
Gauge pressure
(kPa g)
Saturated
Temp. °C
Gauge pressure
(kPa g)
-20
297
0
700
20
1344
-19
312
1
726
21
1384
-18
328
2
752
22
1425
-17
345
3
779
23
1467
-16
361
4
807
24
1509
-15
379
5
835
25
1596
-14
397
6
864
26
1552
-13
415
7
894
27
1641
-12
434
8
924
28
1687
-11
453
9
956
29
1734
-10
473
10
987
30
1781
-9
493
11
1020
31
1830
-8
514
12
1053
32
1880
-7
535
13
1087
33
1930
-6
557
14
1121
34
1981
-5
579
15
1156
35
2034
-4
602
16
1192
36
2087
-3
626
17
1229
37
2142
-2
650
18
1267
38
2197
-1
674
19
1305
39
2253
40
2311
51
3017
62
3874
41
2369
52
3088
63
3961
42
2429
53
3161
64
4049
43
2490
54
3234
65
4138
44
2551
55
3310
66
4229
45
2614
56
3386
67
4322
46
2678
57
3464
68
4416
47
2744
58
3543
69
4512
48
2810
59
3624
70
4610
49
2878
60
3706
-
-
50
2947
61
3789
-
-
The units use high-pressure R-410A refrigerant (the unit operating pressure is above 40 bar, the pressure at 35°C
air temperature is 50% higher than for R-22). Special equipment must be used when working on the refrigerant
circuit (pressure gauge, charge transfer, etc.).