Monobloc Outdoor Unit Installation Manual
7.8.7 Electrical connection to the Monobloc outdoor unit
• Ensure electrical circuits are isolated before commencing work
• Remove the side cover and the electrical box cover from the Monobloc outdoor unit
• The electrical power cable, for the Monobloc outdoor unit, must be sized in accordance Local, National
and International regulations. Please refer to “Cable specifications (power)” for guidance
• Connect the electrical power cable to Terminal TB X1 as shown below
7.8.8 Electrical connection for the remote controller
•
The remote controller must be installed indoors by the installer
•
Connect the remote controller to TB X2, on the Monobloc outdoor unit, in accordance with diagram shown
above
•
Care should be taken when connecting the remote controller as the device is polarity conscious.
Check the polarity of the connections before switching on the power to the system
Input
power
Leakage
breaker
30 mA
Outdoor unit
360 – 440V
3N~ 50Hz
Polarity
WUI (Remote)
OV
WUI
WUI
Out 12 VAC
WUI +12V
WUI 0V