43
Monobloc Outdoor Unit Installation Manual
No.
Step
Parameter Description
Para No.
Range
Default
40
Climatic
Curve
Settings
Heat Minimum OAT (°C)
582
-30 ~ 10
-7.0
41
Heat Maximum OAT (°C)
583
10 ~ 30
20
42
Heat Min Water Setpoint (°C)
584
20 ~ 40
20
43
Heat Max Water Setpoint (°C)
585
30 ~ 60
38
44
Cool Clim Curve Select:
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve using the following parameters (P587 to P590)
1 = Cooling Climatic Curve #1
2 = Cooling Climatic Curve #2
586
-1 ~ 2
-1
45
Cool Minimum OAT (°C)
587
0 ~ 30
20
46
Cool Maximum OAT (°C)
588
24 ~ 46
35
47
Cool Min Water Setpoint (°C)
589
5 ~ 20
10
48
Cool Max Water Setpoint (°C)
590
5 ~ 20
18
Drying Mode Codes
49
Floor drying
mode
Drying Starting Setpoint (°C)
595
20 ~ 40
20
50
Drying Warm-up days
596
0 ~ 99
3
51
Drying Ramp-up days
597
0 ~ 99
4
52
Drying Hold-up days
598
0 ~ 99
4
Backup Configuration Codes
53
Backup
configuration
Backup Type
0 = No backup
1 = Booster by 1 Electric Heating Stage (EH1)
2 = Booster by 2 Electric Heating Stages (EH1/EH2) *
3 = Booster by 3 Electric Heating Stages with 2 outputs (EH1/EH2) *
4 = Booster by 3 Electric Heating Stages with 3 outputs (EH1/EH2/EH3) **
5 = DHW Backup (EH3) ***
6 = Booster by 1 Electric Heating Stage (EH1) + DHW Backup (EH3) ***
7 = Booster by 2 Electric Heating Stages (EH1/EH2) + DHW Backup (EH3) **
8 = Booster by 3 Electric Heating Stages with 2 outputs (EH1/EH2) + DHW Backup (EH3) **
9 = Backup by Oil or Gas Boiler
* One Customer Discrete Output shall be configured as EH2: [P506] = 10 or [P507] = 10
** Both Customer Discrete Outputs shall be configured as EH2 and EH3: [P506] = 10, [P507] = 11
*** One Customer Discrete Output shall be configured as EH3: [P506] = 11 or [P507] = 11
601
0 ~ 9
0
54
Booster Warm Up Time (min)
602
5 ~ 120
30
55
Booster Delta Temp (°C)
603
1 ~ 20
5
56
Booster OAT Threshold: The backup heating is allowed to run if OAT goes below this threshold
(with 1 K hysteresis). See also the
Backup Type
Parameter (P601). (°C)
604
-30 ~ 15
-7
57
EHS Proportional Gain
605
0.001 ~
10.000
2.000
58
EHS Integral Time (sec)
606
10 ~ 240
30
59
EHS Sampling Time (sec)
607
10 ~ 240
30
Domestic Hot Water Codes
60
DHW
Configuration
Domestic Hot Water Type
0 = No DHW management
1 = Diverting Valve NO 2-points
(valve energized in DHW position)
2 = Diverting Valve NC 2-points
(valve de-energized in DHW position)
3 = Dedicated DHW Circulator or Pump
701
0 ~ 3
0
61
DHW 3-way Valve run time (sec)
702
0 ~ 240
30
62
DHW Priority:
0 = Automatic Priority
1 = Priority to Domestic Hot Water
2 = Priority to Space Heating
703
0 ~ 2
0
63
SHC Minimum Runtime (min)
704
0 ~ 720
20
64
SHC Maximum Runtime
If this parameter is configured to -1, maximum SHC or DHW Runtime is ignored.
Note: If SHC Maximum Runtime is set ([P705], it is also necessary to set DHW Maximum
Runtime [P707]. Otherwise, the unit will
never
switch back to DHW (min)
705
-1 (or 30)
~ 720
60
65
DHW Minimum Runtime (min)
706
0 ~ 720
20