61
Monobloc Outdoor Unit Installation Manual
No.
Step
FC Description
FC No.
Range
Default
Example Set Up
3b
Second
possibility:
control on fixed
LWT setpoint
Heat Climatic Curve Select:
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve
1 to 12 = Heating Climatic Curve #number
581
-1 ~ 12
-1
-1
Heat Home Setpoint
Air setpoint for heating mode when Occupancy mode = Home (°C)
401
20 ~ 60
45
50
Heat Sleep Offset
Air offset for heating mode when Occupancy mode = Sleep (°C)
402
-10 ~ 0
0
-5
Heat Away Offset
Air offset for heating mode when Occupancy mode = Away (°C)
403
-10 ~ 0
-5
-10
Cool Climatic Curve Select
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve
1 to 2 = Cooling Climatic Curve #1number
586
-1 ~ 2
0
-1
Cool Home Setpoint
Air setpoint for cooling mode when Occupancy mode = Home (°C)
407
0 ~ 18
12
18
Cool Sleep Offset
Air offset for cooling mode when Occupancy mode = Sleep (°C)
408
0 ~ 10
0
2
Cool Away Offset
Air offset for cooling mode when Occupancy mode = Away (°C)
409
0 ~ 10
5
5
3c
Third
possibility:
customer
control on
climatic curve
Heat Climatic Curve Select:
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve
1 to 12 = Heating Climatic Curve #number
581
-1 ~ 12
-1
0
Heat Minimum OAT: In heating mode, Customer minimum OAT
582
-30 ~ 10
-7
-20
Heat Maximum OAT: In heating mode, Customer maximum OAT
583
10 ~ 30
20
20
Heat Minimum Water Setpoint: In heating mode, Customer minimum Water
Temperature
584
20 ~ 40
20
20
Heat Maximum Water Setpoint: In heating mode, Customer maximum
Water Temperature
585
30 ~ 60
38
38
Heat Curve Max Setpoint Offset: Heat Maximum Water Setpoint can be
offset by this parameter, to adjust the setpoint to the customer needs (°C)
412
-5 ~ 5
0
5
Cool Climatic Curve Select
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve
1 to 2 = Cooling Climatic Curve #1number
586
-1 ~ 2
-1
0
Cool Minimum OAT: In cooling mode, Customer minimum OAT
587
0 ~ 30
20
22
Cool Maximum OAT: In cooling mode, Customer maximum OAT
588
24 ~ 46
35
35
Cool Minimum Water Setpoint: In cooling mode, Customer minimum Water
Temperature
589
5 ~ 20
10
7
Cool Maximum Water Setpoint: In cooling mode, Customer maximum
Water Temperature
590
5 ~ 20
18
15
Cool Curve Min Setpoint Offset: Cool Min Water Setpoint can be offset by
this parameter, to adjust the setpoint to the customer
413
-5 ~ 5
0
5
9.5 Schematic acronyms
IAT: Indoor Air Temperature
BPHE: Brazed Plate Heat Exchanger
CHWS: Chiller Water System
DHW: Domestic Hot Water
EHS: Electric Heater Stage
EWT: Entering Water Temperature
FCU: Fan Coil Unit
LWT: Leaving Water Temperature
NHC: New Hydronic Control (refer to wiring diagram ‘Main control card’)
OAT: Outdoor Air Temperature
PMV: Pulse Modulating Valve
SHC: Space Heating / Cooling Control
TR: Refrigerant Temperature
UFC: Underfloor Cooling
UFH: Underfloor Heating
WUI: Remote controller - user Interface (Wall-mounted User Interface)