13.0 Sensor Temperature Monitoring Function
Normally when the user interface will have the current
indoor air temperature
and the
air set point
displayed on the screen.
If the system has been configured for water temperature control the user interface will have the current
water temperature
and the
water set point
displayed on the screen.
In addition to these temperatures, WUI gives you the option to check other parameters allowing you to monitor the status of
the units (see table given below). Please note that these parameters (1-15) are in read-only access.
No.
Description
Parameter number
1
Outdoor Air Temp
P001
2
Entering Water Temp
P003
3
Leaving Water Temp
P004
4
Water Control Temp
P052
5
Saturated Suction Temp
P008
6
Suction Temperature
P009
7
Superheat Temperature
P015
8
Superheat Target Temp
P016
9
Discharge Temperature
P010
10
Refrigerant Temperature
P005
11
Requested Compressor Frequency
P022
12
Actual Compressor Frequency
P023
13
Water Control Point
P051
14
Flow Switch Status
P105
15
Safety Switch Status
P104
To display the required parameter
1.
Press and hold the Occupancy key and the Mode key simultaneously for 2 seconds.
2.
The first parameter will be displayed.
3.
Press the Down key or the Up key to switch between all parameters listed in the table above.
4.
To exit the current screen, press and hold the Occupancy key until the home screen is displayed or wait for 30
seconds (screen timeout).
Example: Outdoor Air Temp (Parameter: P001)