Monobloc Outdoor Unit Installation Manual
8.2 Parameter setting list
No.
Step
Parameter Description
Para No.
Range
Default
User Configuration Codes
1
User
configuration
User interface type: Selects type of user interface connected to the system:
0 = No user interface (RC will not initiate communication)
1 = Remote control by contacts
2 = RC remotely installed in the house (Air setpoint)
3 = RC remotely installed in the house (Water setpoint)
521
0 ~ 3
0
2
Parameter access levels: Selects the level of access to internal parameters:
0 = Access to parameters not allowed
1 = Access to User parameters only
2 = Access to User and Service parameters
3 = No use
522
0~3
3
3
Interface communication timeout: If no communication message is received from the User
Interface for more than the timeout delay, the unit will be stopped and the alarm will be activated.
If this parameter is set to 0, the communication timeout is ignored (sec)
NOTE: If P523=0 the communication timeout is ignored
523
0 ~ 240
60
4
RC backlight timeout: The RC backlight is switched OFF when no key is pressed within a
configured period of time:
0 = Backlight always OFF (disabled)
1 = 15 seconds
2 = 30 seconds
3 = 1 minute
4 = 2 minutes
5 = 5 minutes
6 = 30 minutes
7 = Always ON (backlight is always ON)
524
0 ~ 7
2
5
Buzzer on key press: Enables or disables a buzzer when the buttons on the RC are pressed
525
No / Yes
No
6
Interface time broadcast: Allows the RC to broadcast the date and time over the Network bus:
No = RC shall read the Date and Time in the Main Controller
Yes = RC shall broadcast Date and Time over the Network bus
526
No / Yes
Yes
7
Service password: Sets the password to access User and Service Parameters when P522=2
527
0 ~ 9999
120
8
User password: Sets the password to access User parameters when P522=1
528
0 ~ 9999
0
Water Setpoint Codes
9
Water setpoint
Heat home setpoint: These setpoints are used when the Heating Auto Curve is selected - P581
= -1 (°C)
401
20 ~ 60
45
10
Heat sleep offset:Temperature offset applied to the heat home setpoint (P401) for night time
operation (°C)
402
-10~ 0.0
0
11
Heat Away Offset:Temperature offset applied to the heat home setpoint (P401) when the
property is not occupied (°C)
403
-10 ~ 0
-5
12
DHW Eco setpoint;Setpoint temperature for the DHW cylinder when the property is not occupied
(°C)
404
20 ~ 60
45
13
DHW anti- bacteria setpoint: Setpoint temperature for the DHW cylinder used for the anti-
bacteria cycle – used with P714 & P715 (°C)
405
50 ~ 60
60
14
DHW setpoint: Setpoint temperature used for the DHW cylinder during normal operation (°C)
406
30 ~ 60
50
15
Cool home setpoint: These setpoints are used when Cooling Auto Curve is selected – P586 = -1
(°C)
407
0 ~ 18
12
16
Cool sleep offset: Temperature offset applied to the cool home setpoint (P407) for night time
operation (°C)
408
0 ~ 10
0
17
Cool away offset: Temperature offset applied to the cool home setpoint (P407) when the
property is not occupied (°C)
409
0 ~ 10
0
18
Heat hysteresis Heat hysteresis: Determines whether cooling mode should be started or stopped. Used in
conjunction with Control Temp and Control point.
410
0.5 ~ 2.0
1.0
19
Cool hysteresis Cool hysteresis: Determines whether cooling mode should be started or stopped. Used in
conjunction with Control Temp and Control point.
411
0.5 ~ 2.0
0.5
20
Heat curve
maximum
setpoint offset
When using heating climatic curves, the Heat maximum water setpoint (P585) can be offset by
the Heat curve maximum setpoint offset to suit customer needs.
412
-5 ~ 5
0
21
Cool curve
minimum
setpoint offset
When using cooling climatic curves, the Cool minimum water setpoint (P589) can be offset by
the Cool curve minimum setpoint offset to suit customer needs.
413
-5 ~ 5
0