59
Monobloc Outdoor Unit Installation Manual
No.
Step
Figure
FC
Designation
Description
Range
Default
Ex.
7
Main V
ariable speed pump configuration for Header/Follower installation
To configure main pump of Follower 1 unit, the other units of installation must be in mode OFF
(only Follower 1 unit is activated)
Apply procedure “Manage the Header and Follower units with a common user interface” to pass on
Follower 1 status
758 Header / Follower
pump type
0 = No pump control
1 = Common Water Pump (a
pump is installed outside of the
unit on the water loop and is
controlled by the Header unit)
2 = Individual Water Pump:
running according to H/F
Overall Status (P229)
3 = Individual Water Pump:
stopped if unit is satisfied
0 ~ 3
2
2
Determine the minimum pump speed and adjust the pump speed to obtain the expected water flow
rate to allow closure of flow switch (see page 80) – Line “variable speed pump – control on adjustable
constant speed
To configure main pump of Follower 2 unit, the other units of installation must be in mode OFF
(only Follower 2 unit is activated)
Apply procedure “Manage the Header and Follower units with a common user interface” to pass on
Follower 2 status
758 Header / Follower
pump type
0 = No pump control
1 = Common Water Pump (a
pump is installed outside of the
unit on the water loop and is
controlled by the Header unit)
2 = Individual Water Pump:
running according to H/F
Overall Status (P229)
3 = Individual Water Pump:
stopped if unit is satisfied
0 ~ 3
2
2
Determine the minimum pump speed and adjust the pump speed to obtain the expected water flow
rate to allow closure of flow switch (see section 11.4) – Line “variable speed pump – control on
adjustable constant speed
8
The Header unit is then used for all the other configuration points (setpoint…).
To know the status of different Followers, follow the procedure below (refer to
Manage the Header and Follower units with a common user
interface”
9.4.4 Manage the Header unit and Follower units with a common user interface
With the remote controller connected to the Header unit, it is possible to access data of Follower (main screen,
parameter menu...).
The procedure to navigate between the different general status of units and pass from Header to Follower 1, then
to Follower 2 (if existing), then to Follower 3 (if existing), is the following:
To navigate from Header to Follower or Follower to Follower, press and hold the
Occupancy
key and
Up
key
simultaneously for 2 seconds: