Monobloc Outdoor Unit Installation Manual
7.8.9 External electrical connections – external control
JBus / ModBus Controller
As standard the Toshiba Monobloc outdoor units are supplied with a JBus / ModBus controller. The controller
provides a secondary port to be connected to a system network thanks to an RS485 bus. The controller has the
ability to communicate without an amplifier. The length of the bus does not exceed 500m.
Description
Line Spec.
Maximum
Length (m)
Connection Destination
RS-485
connection
2 wire
shielded
500m
NHC PCB
J10
Pin 1
A
+RS485
Pin 2
GND
GND
Pin 3
B
-RS485
Connect the RS-485 network cable to J10 on the Monobloc outdoor unit NHC PCB, using the connector supplied
with the unit.
The following parameters have to be set to configure the JBus / ModBus communication:
1. P761: JBus control enable
2. P762: JBus follower address
3. P646: JBus baud rate
4. P764: JBus frame type
5. P766: JBus communication timeout
Please see section 8.3 for details of the JBus register addresses.
BACnet / LON Gateways:
It is possible to connect the Toshiba Monobloc outdoor unit to either a BACnet or LON system network. These
connections are possible by using a factory fitted gateway, as an optional accessory, and as such have to be
ordered when the order for the Monobloc outdoor unit is placed.
RS-485 Network
RS-485 Network