10.3.1 Predefined Climatic Curves:
COOLING:
If the cooling climatic curve [P586] is configured to “1” or “2”, the water setpoint will be calculated
according to the selected cooling climatic curve.
Two predefined cooling climatic curves are available:
Climatic Curve
Min. OAT
Max. OAT
Min. Water Temp
Max. Water Temp
Application
K1
20°C
40°C
5°C
10°C
FCU
K2
20°C
40°C
10°C
18°C
UFC
•
If OAT is invalid (not transmitted by the Inverter, out of range value, etc.), the Water Setpoint is equal to the
current Min. Water Temp
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the current Max. Water
Temp
•
The climatic curve corresponds to the water setpoint in Home mode. To define the other occupancy
modes, it is necessary to configure Cool Sleep Offset [P408] and Cool Away Offset [P409]:
HEATING:
If the heating climatic curve [P581] is configured to a parameter from “1” to “12”, the water setpoint will
be calculated according to the selected heating climatic curve.
Twelve predefined heating climatic curves are available:
Climatic Curve
Min. OAT
Max. OAT
Min. Water Temp
Max. Water Temp
Application
K1
-7°C
20°C
20°C
38
°C
UFH
K2
-5°C
20°C
20°C
33
°C
Ufh
K3
-9°C
20°C
20°C
45°C
FCU
K4
-8°C
20°C
40°C
50°C
FCU
K5
-5°C
20°C
40°C
55°C
Radiator
K6
0°C
20°C
40°C
60°C
Radiator
K7
-20°C
20°C
22°C
42°C
FCU
K8
-20°C
20°C
23°C
55°C
Radiator
K9
-12.7°C
20°C
24°C
60°C
Radiator
K10
-5.9°C
20°C
25°C
60°C
Radiator
K11
-1.5°C
20°C
26°C
60°C
Radiator
K12
3.5°C
20°C
27°C
60°C
Radiator
W
ater Setpoint (
°C
)
OAT (°C)
Cooling Climatic Curves in function of occupancy mode
Home
Sleep
Away
Cooling Climatic Curves
W
ater Setpoint (
°C
)
OAT (°C)
Содержание Estia RUA-CP1701H
Страница 93: ......
Страница 94: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410101 ...