33
Monobloc Outdoor Unit Installation Manual
7.8.11 External electrical connections – analogue inputs (resistance)
Function
Description
Set Up Parameter
AI#01
DHW cylinder temperature sensor
P719
AI#02
Chiller water system temperature sensor
-
AI#04
Outdoor air temperature sensor
P511
7.8.12 External electrical connections – digital outputs (230VAC Triac)
Function
Description
DO#06
DHW 3-way diverting valve
DO#07
Electrical heater EH#1 / boiler ON/OFF
DO#08
User defined function
DO#09
User defined function
3-way valve (diverter) connection
The 3-way diverter valve is used to select either domestic hot water or space heating operation
Recommended valve specification:
•
Kvs = 16
•
Max. Temperature = 150°C
•
L-Port style
2 Types of 3-way valve (diverter) can be used:
•
2-Wire (Spring Return)
•
3-Wire SPST
2-Wire (Spring Return)
In
resistence,
DHW Tank Temperature Sensor
Chiller water System Temperature Sensor
Outdoor Air Temperature Sensor
Ground-Sensor
DHW-V diverting valve
Electrical Heater EH#1/Boiler-On/Off
Customized
Customized
Neutral
Neutral
Triac
230 VAC
Triac
Out 230 V
AC
Neutral
Neutral