ACE-tronics G9 ASD Installation and Operation Manual
109
V/I Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets V/I Input Point 1 Frequency (
F202
) and is the frequency
that is associated with the setting of V/I Input Point 1 Setting (
F201
) when
operating in the Speed Control mode.
See
V/I Input Point 1 Setting
(
F201
) for additional information on this setting.
Direct Access Number — F202
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
V/I Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with V/I Input Point 2
Frequency
(
F204
) when operating in the Speed control mode or is associated
with the V/I Input Point 1 Rate (
F205
) when operating in the Torque Control
mode.
This value is entered as 0% to 100% of the V/I input signal range.
See V/I Input Point 1 Setting (
F201
) for additional information on this setting
when used for Speed control.
See V/I Input Point 1 Rate (
F205
) for additional information on this setting
when used for Torque Control.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
V/I Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets V/I Input Point 2 Frequency and is the frequency that is
associated with the setting of V/I Input Point 2 Setting (
F203
) when operating
in the Speed Control mode.
See V/I Input Point 1 Setting (
F201
) for additional information on this setting.
Direct Access Number — F204
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
F202
F204
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]