ACE-tronics G9 ASD Installation and Operation Manual
189
FM Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See
F005
for additional information on this setting.
Settings:
0 – 10 V
0 – 20 mA
Direct Access Number — F681
Parameter Type — Selection List
Factory Default — 0–10V
Changeable During Run — No
FM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See
F005
for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number — F682
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
FM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.
Set the function of
F005
to zero and then set this parameter to zero for proper
operation.
See
F005
for additional information on this setting.
Direct Access Number — F683
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
AM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the AM output terminal.
The AM output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F670
for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number — F685
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
AM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at
F670
to zero and then set this parameter to zero for
proper operation.
See
F670
for additional information on this setting.
Direct Access Number — F686
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %