ACE-tronics G9 ASD Installation and Operation Manual
173
S-Pattern Acceleration Lower-Limit Adjustment
Program
Special
Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter setting modifies the
acceleration rate for the lower part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
F502 on pg. 170
for additional information on this setting.
Direct Access Number — F506
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %
S-Pattern Acceleration Upper-Limit Adjustment
Program
Special
Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter setting modifies the
acceleration rate for the upper part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
F502 on pg. 170
for additional information on this setting.
Direct Access Number — F507
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %
S-Pattern Deceleration Lower-Limit Adjustment
Program
Special
Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter setting modifies the
deceleration rate for the lower part of the deceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
F502 on pg. 170
for additional information on this setting.
Direct Access Number — F508
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %
S-Pattern Deceleration Upper-Limit Adjustment
Program
Special
Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter setting modifies the
deceleration rate for the upper part of the deceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
F502 on pg. 170
for additional information on this setting.
Direct Access Number — F509
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %
Acceleration Time 3
Program
Special
Accel/Decel 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the #3 Acceleration profile. The
Accel/Decel pattern may be set using
F502
. The minimum Accel/Decel time
may be set using
F508
.
Note:
An acceleration time shorter than that which the load will allow
may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings may
lengthen the actual acceleration times.
Direct Access Number — F510
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F506
F510
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]