ACE-tronics G9 ASD Installation and Operation Manual
119
RX2 Option (AI1) Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
Note:
The Expansion IO Card Option 1 option board (P/N ETB003Z)
is required to use this terminal.
This parameter sets the RX2 (AI1) input level that is associated with RX2
(AI1) Input Point 1 Frequency when operating in the Speed Control mode or
is associated with the RX2 (AI1) Input Point 1 Rate when operating in the
Torque Control mode.
RX2 (AI1) Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the RX2 (AI1) input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
RX2.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RX2 (AI1) input terminal:
• Set RX2 (AI1) Input Point 1 Frequency (
F223
).
• Set RX2 (AI1) Input Point 1 Setting (
F222
) — the input analog signal
level that corresponds to the speed setting at RX2 (AI1) Input Point 1
Frequency.
• Set RX2 (AI1) Input Point 2 Frequency (
F225
).
• Set RX2 (AI1) Input Point 2 Setting (
F224
) — the input analog signal
level that corresponds to the speed setting at RX2 Input Point 2
Frequency.
• Provide a Run command (F and/or R).
Once set, as the RX2 (AI1) input voltage changes, the ASD output speed and/or
torque will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the RX2 (AI1) input
signal range.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for
additional information on the function of this terminal.
See parameter
F476
and
F477
for information on fine-tuning the
responsiveness of this terminal.
Direct Access Number — F222
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Frequency Settings
F222
F222