ACE-tronics G9 ASD Installation and Operation Manual
Command Mode
Program
Fundamental
Standard Mode Selection
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc. The
Override feature may supersede the Command Mode Selection setting (see
Command and Frequency Mode Control on pg. 47
).
Settings:
Terminal Board
EOI Keypad
RS485
Communication Option Board
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Terminal Board
Changeable During Run — No
Frequency Mode 1
Program
Fundamental
Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting (see
Command and Frequency Mode
Control on pg. 47
and
F200
for additional information on this feature).
Note:
Only bolded items from the Settings list below may be placed in
the Override mode.
Settings:
V/I
RR
RX
EOI Keypad
RS485
Communication Option Board
RX2 Option (AI1)
Option V/I
UP/DOWN Frequency
Pulse Input (Option)
Pulse Input (Motor CPU)
Binary/BCD Input (Option)
Direct Access Number — F004
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No
Frequency
Mode 1
F003
F004