ACE-tronics G9 ASD Installation and Operation Manual
27
a motor by setting a limit. The gain and bias of this terminal may be adjusted for application-specific
suitability (see
F216
–
F221
). See
Figure 20 on pg. 30
for an electrical depiction of the RX terminal.
V/I
— The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input is to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously. SW2 must be set to V or I to receive a voltage or current, respectively (see
Figure
8 on pg. 24
). Terminal scaling is accomplished via
F201
–
F206
. The gain and bias of this terminal may
be adjusted for application-specific suitability (see
F470
and
F471
).
P24
— +24 VDC at 200 mA power supply for customer use.
PP
— The function of output PP is to provide a 10 VDC/10 mADC max. output that may be divided
using a potentiometer or other transducer. The tapped voltage is applied to the RR input to provide
manual control of the RR programmed function.
OUT1
— The default function assigned to this terminal is Output Low Speed. This output may be
programmed to provide an indication (open or closed) that any one of the functions listed in
Table 10 on
pg. 242
has occurred or is active. This function may be used to signal external equipment or to activate
the brake (see
F130
). The OUT1 terminal is rated at 2 A/120 VAC and 2 A/30 VDC.
OUT2
— The default function assigned to this terminal is ACC/DEC Complete. This output may be
programmed to provide an indication (open or closed) that any one of the functions listed in
Table 10 on
pg. 242
has occurred or is active. This function may be used to signal external equipment or to activate
the brake (see
F131
). The OUT2 terminal is rated at 2 A/120 VAC and 2 A/30 VDC.
FP
— The default function of this output terminal is to output a series of pulses at a rate that is a
function of the output frequency of the ASD (50 mA max. at 1.0 kHz to 43.3 kHz). As the output
frequency of the ASD goes up so does the FP output pulse rate. This terminal may be programmed to
provide an output pulse rate that is proportional to the magnitude of any of the user-selected items from
Table 8 on pg. 240
. For additional information on this terminal see
F676 on pg. 188
.
AM
— This output terminal produces an output voltage that is proportional to the output frequency of
the ASD or of the magnitude of the function assigned to this terminal. This terminal may be
programmed to provide an output voltage that is proportional to the magnitude of any of the user-
selected items from
Table 8 on pg. 240
. For additional information on this terminal see
F670 on pg.
186
.
FM
— This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. This terminal may
be programmed to provide an output current or voltage that is proportional to the magnitude of any of
the user-selected items from
Table 8 on pg. 240
. For additional information on this terminal see
F005 on
pg. 81
. The Voltage/Current output selection is performed at
F681
.
BRAKE-A
— One of two normally open contacts that, under user-defined conditions, connect to
BRAKE-C.
BRAKE-B
— One of two normally closed contacts that, under user-defined conditions, connect to
BRAKE-C.
P24